CHAPTER 4: UFLY SETUP AND PROGRAMMING

4.3.2 0-to-10-Volt Remote Setpoint Mode Operation Configuration

The 0-to-10-volt Remote Setpoint Mode is configured as follows:
1. Access Device Management from Main Menu; select hcm > Parameter Settings
2. Scroll to Parameter 799. Set Parameter 799 = 2.
• Parameter 799 defines the functionality of terminals 6/7 of connector Y2 on the
Input/Output box.
• When set to "2", the terminals will accept a 0-10V Remote setpoint input.
• When set to "1" (Default value), the terminals will accept an outdoor air sensor – see
Chapter 4.1.
OMM-0159_A_A • 6/28/2022