Watts AERCO EXT Installation, Operation & Maintenance Manual page 47

Modulex ufly controller & bcm
Table of Contents

Advertisement

Ufly Controller and BCM for Modulex EXT
CHAPTER 6: BOILER COMMUNICATIONS MODULE (BCM)
2. Scroll to Parameter 376. This parameter defines the functionality of terminals Y2 TA/9. Set
Parameter 376 = 3 to automatically activate the BCM as a backup controller.
NOTE: Terminals Y2 TA/9 can be used for automatic activation of BCM as a backup controller
described above OR for enable/disable functionality not both. See Section 4.5 for setting of
Parameter 376 for enable/disable functionality.
OMM-0159_A_A • 6/28/2022
Technical Support • (800) 526-0288 • Mon-Fri, 8 am - 5 pm EST
Page 47 of 83