CHAPTER 3: OPERATION, MENU & PARAMETERS
6. Click on the Request +/- buttons to set the boiler manual firing rate desired.
7. If desired, user can select which burner(s) to run during manual firing rate function.
a. Select one of the available burners
b. Note that the next screen shown is for the selected Burner.
c. Toggling the Activate button enables the selected burner to run during manual
firing rate.
d. The Current Fire Rate of activated burners will equal the manual firing rate set in
the Boiler Screen.
8. To disable the Sweeper/Manual Firing Rate Function, press the Home button

3.5.2 Manual Setpoint Function

1. Click on the Manual Setpoint button
2. Toggling the Activate button allows the boiler to be operated via manual setpoint.
Setpoints in Heating or DHW Mode are ignored when Manual Setpoint is activated.
OMM-0159_A_A • 6/28/2022
.
icon. This will show an Activate Button.
Technical Support • (800) 526-0288 • Mon-Fri, 8 am - 5 pm EST
.