Table 1.2: Monitoring Function
Commands / signals that can be received
by the Converter Module from the
Controller.
• Turn On/Off
• HVSD Reset
• Current Limit Adjustment
• Voltage Adjustment
• Fan Speed Control Enable/Disable
• HVSD Threshold
1.2.6 Mechanical Specifications
•
Weight: 1.13kg (2.49 lbs).
•
Dimensions (H x W x D): 1.65" (42mm) x 3.33" (84.5mm) x 10.2" (260mm).
•
Local Controls: None.
•
Local Status and Alarm Indicators:
a)
Power (Green)
b)
Protection (Yellow)
c)
Alarm (Red)
2 Operation
2.1 Local Indicators
Location and Identification: Refer to Figure 2.1.
Description: There are three (3) indicators located on the converter's front panel. The functions of these indicators are as shown in
Table 2.1.
NOTE!
DC voltage must be present at the converter output terminals (from battery or an operating converter) or DC voltage
at the input terminals.
Information gathered by the Controller from the
Converter Module.
• Output Voltage
• Output Current
• Current Limit Setting
• Temperature
• Over Voltage Setting
• On/Off Status
• Fault Alarms, such as:
HVSD
Fan Fail
• EEPROM Failure
• Protection Alarms, such as:
Input Voltage Protection
High Temperature Protection
• Thermal Derating
• Address
• Code
• Date
• Software Version
• Hardware Version
• Imbalance Output Current
Vertiv™ NetSure™ DC/DC Converter Module User Manual
7