NetSure™ Supervision Module for Distribution Unit Plus Installation and User Manual (UM10010507), Revision A Specification Number: 10010507 Model Number: SM-DU+ with Enclosure...
Page 2
This document may contain confidential and/or proprietary information of Vertiv Group Corp., and its receipt or possession does not convey any right to reproduce, disclose its contents, or to manufacture or sell anything that it may describe. Reproduction, disclosure, or use without specific authorization from Vertiv Group Corp.
SAFETY! Informs the reader of general safety information, reminders, precautions, or policies not related to a particular source of hazard or to fire safety. (ISO, ANSI, OSHA) Vertiv | NetSure™ Site Monitoring Unit Installation & User Manual (UM10010507) | Rev. A...
ALERT! Installation or removal of equipment containing static sensitive components requires careful handling. Before handling any equipment containing static sensitive components, read and follow the instructions contained on the Static Warning Page. Vertiv | NetSure™ Site Monitoring Unit Installation & User Manual (UM10010507) | Rev. A...
If necessary to repair equipment containing static sensitive components, wear an appropriately grounded wrist strap, work on a conductive surface, use a grounded soldering iron, and use grounded test equipment. Vertiv | NetSure™ Site Monitoring Unit Installation & User Manual (UM10010507) | Rev. A...
Fourteen (14) Fuse Alarm (Bus- base of 0 VDC, >10 VDC alarm, <10 VDC normal). Input Signals Twenty-Five (25) Load Shunts (25 mV DC to 75 mV DC Shunt) Dimensions See Figure 2. Vertiv | NetSure™ Site Monitoring Unit Installation & User Manual (UM10010507) | Rev. A...
Page 8
Figure 2: Dimensions 10.00 4.76 Bottom 2.57 Left Side Front Right Side 9.43 Diameter 0.14” (4-places) 3.86 Notes: 1. All dimensions are in inches, unless otherwise specified. Vertiv | NetSure™ Site Monitoring Unit Installation & User Manual (UM10010507) | Rev. A...
RS232 Green Indicator SM-DU+ Circuit Board 8 7 6 5 4 3 2 1 8 7 6 5 4 3 2 1 Switch SW1 Switch SW2 Vertiv | NetSure™ Site Monitoring Unit Installation & User Manual (UM10010507) | Rev. A...
Page 10
Shunt Current: 200 A Shunt Current: 300 A Shunt Current: 400 A Shunt Current: 1000 A Shunt Current: 1500 A Shunt Current: 2000 A Note 1: Default Setting Vertiv | NetSure™ Site Monitoring Unit Installation & User Manual (UM10010507) | Rev. A...
Page 11
Address 6# (Setting for 6th SM-DU+ in System) Address 7# (Setting for 7th SM-DU+ in System) Address 8# (Setting for 8th SM-DU+ in System) 19200 (note 1) 9600 Note 1: Default Setting Vertiv | NetSure™ Site Monitoring Unit Installation & User Manual (UM10010507) | Rev. A...
Recommended Lug: #6 Spade to the SM-DU+ Assembly. Distance between Barriers: 0.30” Torque: 9.0 in-lbs. -48V: Red Wire RTN: Black Wire P/N 557012 Cable Assembly (provided) Vertiv | NetSure™ Site Monitoring Unit Installation & User Manual (UM10010507) | Rev. A...
Connect a termination resistor such as P/N 561768 to the last SM-DU+ assembly in the NCU CAN bus. Connect to CAN_H and CAN_L terminals along with the CAN_H and CAN_L leads factory connected to the terminal block. See Figure 7. Vertiv | NetSure™ Site Monitoring Unit Installation & User Manual (UM10010507) | Rev. A...
Page 16
Screw: #6-32 Philslot CAN bus terminal block and Recommended Lug: #6 Spade place it here (or use P/N Distance between Barriers: 0.30” 561768 termination resistor). Torque: 9.0 in-lbs. Vertiv | NetSure™ Site Monitoring Unit Installation & User Manual (UM10010507) | Rev. A...
Configuring the NCU SM-DU+ Parameters Refer to the NCU controller manual (UM1M830BNA) for detailed instructions on how to program the monitored inputs to the SM-DU+ assembly. Vertiv | NetSure™ Site Monitoring Unit Installation & User Manual (UM10010507) | Rev. A...