eSure™
Rectifier Module
User Manual
Specification Number: 1R481000e3
Model Number: R48-1000e3

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the eSure R48-1000e3 and is the answer not in the manual?

Questions and answers

Subscribe to Our Youtube Channel

Summary of Contents for Vertiv eSure R48-1000e3

  • Page 1 eSure™ Rectifier Module User Manual Specification Number: 1R481000e3 Model Number: R48-1000e3...
  • Page 2 The information contained in this document is subject to change without notice and may not be suitable for all applications. While every precaution has been taken to ensure the accuracy and completeness of this document, Vertiv assumes no responsibility and disclaims all liability for damages resulting from use of this information or for any errors or omissions.
  • Page 3: Table Of Contents

    2.3 Rectifier High Voltage Shutdown and Lockout Restart ................................. 12 2.4 Rectifier Current Limit ................................................12 2.5 Installing Rectifiers..................................................12 3 Troubleshooting and Repair ............................13 3.1 Troubleshooting ................................................... 13 3.2 Replacement Procedures ..............................................15 Proprietary and Confidential © 2022 Vertiv Group Corp.
  • Page 4: Admonishments Used In This Document

    (ISO) SAFETY! Informs the reader of general safety information, reminders, precautions, or policies not related to a particular source of hazard or to fire safety. (ISO, ANSI, OSHA) Proprietary and Confidential © 2022 Vertiv Group Corp.
  • Page 5: Important Safety Instructions

    Refer to Section 4154 (provided with your customer documentation) for Safety and Regulatory Statements. Déclarations de Sécurité et de Réglementation Reportez-vous à la Section 4154 (fourni avec les documents de votre client) pour les déclarations de sécurité et de réglementation. Proprietary and Confidential © 2022 Vertiv Group Corp.
  • Page 6 Vertiv™ eSure™ Rectifier Module User Manual This page intentionally left blank. Proprietary and Confidential © 2022 Vertiv Group Corp.
  • Page 7: Introduction

    Output Characteristics: Refer to Figure 1.1 for a graph of output voltage vs. output current. Figure 1.1 Output Voltage vs. Output Current Output Voltage vs. Output Current at Max. Power Output Current (A) Proprietary and Confidential © 2022 Vertiv Group Corp.
  • Page 8 70C the rectifier module will linearly derate to 800W if the AC input is 200VAC to 250Vac and the DC output voltage setting of the rectifier module is 50VDC to 56VDC. Proprietary and Confidential © 2022 Vertiv Group Corp.
  • Page 9 Wide Band Noise: Wideband noise emission is < 250 mV peak to peak between 0 Hz – 100 MHz, and < 50 mV rms in any 3 kHz band 10 KHz – 20 MHz. Proprietary and Confidential © 2022 Vertiv Group Corp.
  • Page 10 System output is initially adjusted to 53.5 VDC as measured at the system sense point at 50 % of full load and nominal input. “Percent of Full Load” refers to percent of 18.69 amperes. Proprietary and Confidential © 2022 Vertiv Group Corp.
  • Page 11 1.130 270.31 267.41 0.989 93.53 59.02 2.200 527.88 525.05 0.997 95.14 86.99 240 VAC 3.290 789.54 787.32 0.997 95.09 131.90 4.417 1059.25 1057.09 0.998 94.42 201.38 4.581 1098.85 1096.42 0.998 94.11 220.40 Proprietary and Confidential © 2022 Vertiv Group Corp.
  • Page 12 Relative Humidity: This rectifier is capable of operating in an ambient relative humidity range of 0 % to 90 %, non- condensing. • Altitude: 2000 m (6560 ft) at full power (power limited for heights above 2000 m). Proprietary and Confidential © 2022 Vertiv Group Corp.
  • Page 13 Constant Voltage Mode: For any initial output voltage setting from 42 VDC to 58 VDC, output voltage remains constant regardless of load. This is the normal operating condition, in which loads are being supplied and batteries are float charged. Proprietary and Confidential © 2022 Vertiv Group Corp.
  • Page 14 LEDs on the rectifier extinguish, then turning power to the rectifier on or re-inserting the rectifier). If the rectifier does not experience a high voltage condition before the HVSD restart timer expires, the restart circuit is reset. Proprietary and Confidential © 2022 Vertiv Group Corp.
  • Page 15 Monitoring Function: The rectifier has a built-in advanced DSP that monitors and controls the operation of the rectifier. The DSP also communicates with the controller in real time through the CAN bus. Table 1.5 lists the different commands and information exchanged between the rectifier and the controller. Proprietary and Confidential © 2022 Vertiv Group Corp.
  • Page 16 Millimeters: 43.6 (Height) X52 (Width) X 152 (Depth) Inches: 1.7 (Height) X 2.0 (Width) X6.0 (Depth) • Weight: 0.6 kg (1.3 lbs) • Indicators: Power (Green LED) Protection (Yellow LED) Alarm (Red LED) Proprietary and Confidential © 2022 Vertiv Group Corp.
  • Page 17: Operation

    Flashing power). Severe load sharing imbalance. Rectifier output disabled for any reason, including overvoltage Alarm shutdown and internal output fuse open. (Red) Rectifier addresses contradictory. Flashing Fan not operating (rectifier shuts down). Proprietary and Confidential © 2022 Vertiv Group Corp.
  • Page 18: Rectifier High Voltage Shutdown And Lockout Restart

    Repeat the above steps for each rectifier being installed in the system. After the rectifiers are physically installed in the mounting shelf(s), they are ready for operation immediately after power is supplied to them. Proprietary and Confidential © 2022 Vertiv Group Corp.
  • Page 19: Troubleshooting And Repair

    The fault indicators that can be displayed by the rectifier are as follows. Refer to Table 3.1 for a list of possible causes and corrective actions. • Power Indicator (Green) Off • Protection Indicator (Yellow) ON Proprietary and Confidential © 2022 Vertiv Group Corp.
  • Page 20 (Red) On replace the rectifier. fuse open. Rectifier addresses contradictory. Replace the rectifier. Alarm Indicator Fan not operating (rectifier shuts Replace the rectifier. (Red) Flashing down). Proprietary and Confidential © 2022 Vertiv Group Corp.
  • Page 21: Replacement Procedures

    Verify that the rectifiers are operating normally. Enable the external alarms, or notify appropriate personnel that this procedure is finished. Ensure that there are no local or remote alarms active on the system. Proprietary and Confidential © 2022 Vertiv Group Corp.
  • Page 22 Vertiv™ eSure™ Rectifier Module User Manual This page intentionally left blank. Proprietary and Confidential © 2022 Vertiv Group Corp.
  • Page 23 Vertiv™ eSure™ Rectifier Module User Manual Connect with Vertiv on Social Media https://www.facebook.com/vertivI https://www.instagram.com/vertiv/ https://www.linkedin.com/company/vertiv/ https://www.twitter.com/vertiv/ Proprietary and Confidential © 2022 Vertiv Group Corp.
  • Page 24 Vertiv.com | Vertiv Headquarters, 1050 Dearborn Drive, Columbus, OH, 43085, USA © 2022 Vertiv Group Corp. All rights reserved. Vertiv™ and the Vertiv logo are trademarks or registered trademarks of Vertiv Group Corp. All other names and logos referred to are trade names, trademarks or registered trademarks of their respective owners. While every precaution has been taken to ensure accuracy and completeness here, Vertiv Group Corp.