Vertiv Liebert iCOM Installer/User Manual
Vertiv Liebert iCOM Installer/User Manual

Vertiv Liebert iCOM Installer/User Manual

Intelligent communication and monitoring for liebert crv
Hide thumbs Also See for Liebert iCOM:
Table of Contents

Advertisement

Liebert® iCOM™
Intelligent Communication and Monitoring
for Liebert CRV
Installer/User Guide

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the Liebert iCOM and is the answer not in the manual?

Questions and answers

Summary of Contents for Vertiv Liebert iCOM

  • Page 1 Liebert® iCOM™ Intelligent Communication and Monitoring for Liebert CRV Installer/User Guide...
  • Page 2 Technical Support Site If you encounter any installation or operational issues with your product, check the pertinent section of this manual to see if the issue can be resolved by following outlined procedures. For additional assistance, visit https://www.VertivCo.com/en-us/support/...
  • Page 3: Table Of Contents

    3 Service Operation 3.1 Editing setpoints for the cooling unit 3.1.1 Configuring Temperature Setpoints 3.1.2 Temperature Control – Temperature Setpoints and Compressor Operation 3.1.3 Compressor Control by Temperature Proportional Band 3.1.4 Configuring high/low-limit setpoints 3.1.5 Configuring humidity setpoints 3.1.6 Humidity Control Vertiv | Liebert® iCOM™ Installer/User Guide |...
  • Page 4 6.3.1 Manually Rotating the Operating and Stand-by Units 7 External Monitoring and Building-management Systems 7.1 Building Management Systems Operation 7.1.1 Adjusting Monitoring (IntelliSlot) Settings 7.1.2 Setting BMS Control Settings 8 Configuring Auxiliary Devices 8.1 Fluid-temperature Monitoring Vertiv | Liebert® iCOM™ Installer/User Guide |...
  • Page 5 11.3 Customizing Panel Content 11.3.1 Accessing panel-edit mode 11.3.2 Replacing Panel Content 11.3.3 Resizing and Moving a panel 11.3.4 Removing a panel 11.3.5 Adding content to a status panel 11.3.6 Moving content in a status panel Vertiv | Liebert® iCOM™ Installer/User Guide |...
  • Page 6 11.3.8 Selecting Graphical/List view for status and dates 11.4 Customizing parameter and field labels 11.4.1 Exporting, Importing and Customizing labels using a text editor 12 Liebert iCOM Hardware Installation 12.1 Installing Wired Remote Sensors 12.1.1 Setting DIP switches and labeling 2T sensors 12.1.2 Terminating the last sensor on the CANbus link...
  • Page 7: Getting Started With Icom

    Thermal Management units. It is available factory-installed on new units and assemblies or may be retrofitted in existing units. 1.1 Touchscreen Display and User Interface The Liebert iCOM touchscreen and user interface speeds set up and installation and simplifies control of Liebert thermal-management units, literally putting cooling-system monitoring and management at your fingertips.
  • Page 8 Teamwork-mode icon. In a panel with “Status” content, the Teamwork Mode icon indicates the mode selected. For details and descriptions of the teamwork controls, see Teamwork Modes on page 69. Control header. Controls to access the user and service menus. See Control Header on page 11. Vertiv | Liebert® iCOM™ Installer/User Guide |...
  • Page 9: Touchscreen Status Dial

    Right control sensor. Sensor selected for control. Lower-center sensor reading. Single or multiple sensor readings. Cycle through readings by touching the displayed reading. Left control sensor. Sensor selected for control. Left setpoint. Setpoint and control sensor used for setpoint calculations. Vertiv | Liebert® iCOM™ Installer/User Guide |...
  • Page 10: Dial Background-Color Status Indication

    Figure 1.3 Dial background colors ITEM DESCRIPTION Sensor reading is within threshold limits. Unit is powered-off. Sensor reading is above threshold limit. Sensor reading is below threshold limit Vertiv | Liebert® iCOM™ Installer/User Guide |...
  • Page 11: Control Header

    2. Touch the numbers for your PIN, then touch Enter. Depending on the PIN entered and your level of access, the User and/or Service options are accessible. See Accessing the User and Service Functions on page 15. Vertiv | Liebert® iCOM™ Installer/User Guide |...
  • Page 12: Powering-On The Thermal Management Unit

    DISPLAY OFF Unit is turned Off at the iCOM display. See Powering-on the Thermal Management Unit above ALARM In stand-by because of an active alarm on the unit. See Viewing Unit Alarms on page 21. STANDBY Vertiv | Liebert® iCOM™ Installer/User Guide |...
  • Page 13: Powering-Off The Thermal Management Unit

    “on/closed.” If one is “off/open,” the unit turns off. MONITORING Turned-off by remote monitoring system. Check the remote monitoring device or call Vertiv™ technical support for assistance. RESTART Not yet operational after a power cycle because the restart-delay timer is active.
  • Page 14: Setting The Date And Time

    To locate the firmware version of the iCOM control board, see Updating iCOM control-board firmware on page 83. Touch , then The User menu opens. 2. Touch About. The ABOUT panel opens. Vertiv | Liebert® iCOM™ Installer/User Guide |...
  • Page 15: Accessing The User And Service Functions

    Custom Labels—see Customizing parameter and field labels on page 106. • Display Properties—see Setting general display properties on page 101. Total Run Hours Opens the RUN HOURS panel. See Managing Run Hours for a Component on page 24. Vertiv | Liebert® iCOM™ Installer/User Guide |...
  • Page 16: Service Menu

    BMS Setup—See Building Management Systems Operation on page 75. Scheduler Opens the SCHEDULER panel. See Scheduling Condenser and Cooling-unit Tasks on page 44. Options Setup Opens the OPTIONS SETUP panel. See Setting General Thermal-management Unit Options page 46. Vertiv | Liebert® iCOM™ Installer/User Guide |...
  • Page 17 Turn Unit On/Off Depending on unit’s status, open the TURN UNIT ON or TURN UNIT OFF dialog. See Powering-on the Thermal Management Unit on page 12, or Powering-off the Thermal Management Unit page 13. Vertiv | Liebert® iCOM™ Installer/User Guide |...
  • Page 18 This page intentionally left blank. Vertiv | Liebert® iCOM™ Installer/User Guide |...
  • Page 19: User Operation

    The adjusted humidity sensor reading displays on the screen. • Dewpoint = Percent of humidification/dehumidification is determined by the difference between the dewpoint calculated from the humidity-sensor reading and the dewpoint setpoint. Vertiv | Liebert® iCOM™ Installer/User Guide |...
  • Page 20: Editing Temperature Setpoints

    Remote Sensor = Temperature control is based on the temperature reading(s) from wired remote sensor(s). See Wired Remote Sensors on page 79. • Return Sensor = Temperature control is based on maintaining the temperature of the air returning to the cooling unit. Vertiv | Liebert® iCOM™ Installer/User Guide |...
  • Page 21: Viewing Unit Alarms

    2. Touch an alarm to display the ALARM DETAILS panel. Alarm fields Alarm Name of the event. Date Date event was logged. Time Time event was logged Alarm-detail fields Alarm Name of the event. Vertiv | Liebert® iCOM™ Installer/User Guide |...
  • Page 22: Silencing An Audible Alarm

    Alarms panel and the LED stops flashing red. NOTE: Acknowledging alarm events does not clear them. To clear an issue, it must be corrected, reset automatically by the controller, or reset manually. Vertiv | Liebert® iCOM™ Installer/User Guide |...
  • Page 23: Viewing The Event Log

    Red dot Unacknowledged alarm event. See Acknowledging Alarms on the previous page. White dot with check-mark overlay Acknowledged event, the cause still exists. White circle Acknowledged event, the cause is cleared. Vertiv | Liebert® iCOM™ Installer/User Guide |...
  • Page 24: Viewing Sensor Data

    NOTE: The REMOTE SENSORS panel must be selected as content to view it. See Replacing Panel Content on page 104. NOTE: Depending on the type of thermal-managment unit, included components, and control settings of your system, the options on your iCOM display may differ. Vertiv | Liebert® iCOM™ Installer/User Guide |...
  • Page 25: Adjusting The Range Of Remote-Sensor Graphs

    2. To remove a sensor graph, touch the X next to the graph. The graph is removed. – or – To return all sensors to the view, touch Reset Layout. 3. Touch Save. The panel is updated. Vertiv | Liebert® iCOM™ Installer/User Guide |...
  • Page 26: Viewing Teamwork, Stand-By, Cascade And Operating Status

    NOTE: You must be logged-in with the Service PIN to edit teamwork mode. See Powering-on iCOM and Logging-in/Unlocking Controls on page 11. Figure 2.1 Teamwork icons ITEM DESCRIPTION No teamwork. Mode 1 - Parallel teamwork Mode 2 - Independent teamwork Mode 3 - Optimized aisle teamwork Vertiv | Liebert® iCOM™ Installer/User Guide |...
  • Page 27: Service Operation

    Considerations when Using PI Temperature Control on page 31. NOTE: Depending on the type of thermal-managment unit, included components, and control settings of your system, all of the options listed may not be available on your iCOM display. Vertiv | Liebert® iCOM™ Installer/User Guide |...
  • Page 28 • Adaptive PID = Auto-tuning PID control loop, can be set for Cooling. Adaptive PID is only available if your system includes a Liebert iCOM-S panel. • Intelligent = percent of cooling/heating determined by programmed logic that simulates manual human control.
  • Page 29: Temperature Control - Temperature Setpoints And Compressor Operation

    If air temperature rises to the end of the proportional band or further, the system operates at 100% capacity to bring the temperature down to the setpoint. • The heating capacity operates in the same way as the air temperature falls below the setpoint. Reheat Control. Vertiv | Liebert® iCOM™ Installer/User Guide |...
  • Page 30 Like the proportional band, the dead band is also divided evenly on each side of the setpoint. • 0% cooling capacity is required from 69° to 71°. • At 71°, the system operates according to the temperature proportional band. Vertiv | Liebert® iCOM™ Installer/User Guide |...
  • Page 31: Compressor Control By Temperature Proportional Band

    Depending on the type of cooling unit, the number and type of compressors varies. The following describes compressor operation along the proportional band for the varying compressor options. Vertiv | Liebert® iCOM™ Installer/User Guide |...
  • Page 32 The compressor starts at 75° when the cooling requirement is 100% and continues to operate until 71° is reached when cooling requirement is 0%. Figure 3.3 Compressor control—1-step capacity DESCRIPTION Single scroll compressor. ½ of proportional band. Deadband. Vertiv | Liebert® iCOM™ Installer/User Guide |...
  • Page 33 50% and it returns to un-loaded operation. Figure 3.4 Compressor control—2-step capacity using 1 scroll compressor with unloaders NUMBER DESCRIPTION Scroll compressor unloaded. Scroll compressor loaded. ½ of proportional band. Deadband. Vertiv | Liebert® iCOM™ Installer/User Guide |...
  • Page 34 5 seconds (0% cooling), • which results in 66% cooling. Essentially, the compressor is “partially-loaded.” Figure 3.5 Digital-scroll compressor operation to provide 66% cooling capacity DESCRIPTION Solenoid de-energized. Solenoid energized. 15-second capacity modulation cycle. Percent loaded. Vertiv | Liebert® iCOM™ Installer/User Guide |...
  • Page 35 The compressor stops when cooling demand decreases to 10%. Figure 3.6 on the next page illustrates digital-scroll compressor operation with the following setpoint parameters: • 70° setpoint • 8° proportional band • 2° dead band Vertiv | Liebert® iCOM™ Installer/User Guide |...
  • Page 36: Configuring High/Low-Limit Setpoints

    2. Touch High/Low Limit Control in the Options list. The HIGH/LOW LIMIT CONTROL secondary panel opens. 3. Adjust the setpoint options, then touch Save. The setpoint is updated. • Touch Cancel to discard the changes. Vertiv | Liebert® iCOM™ Installer/User Guide |...
  • Page 37: Configuring Humidity Setpoints

    NOTE: Depending on the type of thermal-managment unit, included components, and control settings of your system, all of the options listed may not be available on your iCOM display. Humidity Control options Control Dewpoint Dewpoint setpoint. Vertiv | Liebert® iCOM™ Installer/User Guide |...
  • Page 38 Adjusts the activation point of humidifier/dehumidification components based on deviation from setpoint by placing half of the selected value on each side of the humidity-control setpoint. A smaller number causes faster reaction to humidity changes. Vertiv | Liebert® iCOM™ Installer/User Guide |...
  • Page 39: Humidity Control

    Use the proportional and dead-band parameters to control how your cooling unit(s) respond based on the calculated need for humidification/dehumidification. As the return-air humidity deviates from the humidity setpoint, iCOM responds with a humidification or dehumidification capacity of 0% to 100% in 1% increments. Vertiv | Liebert® iCOM™ Installer/User Guide |...
  • Page 40 (Advanced setting: A557) and 100% depending upon required dehumidifying capacity. The display always shows 100% dehumidification. Figure 3.7 Humidity control without a dead band DESCRIPTION ½ of proportional band. ½ of proportional band. Vertiv | Liebert® iCOM™ Installer/User Guide |...
  • Page 41: Configuring Fan Setpoints

    The SETPOINTS panel opens. 2. Touch Fan Control in the Options list. The FAN CONTROL secondary panel opens. 3. Adjust the setpoint options, then touch Save. The setpoint is updated. • Touch Cancel to discard the changes. Vertiv | Liebert® iCOM™ Installer/User Guide |...
  • Page 42: Manual Fan-Speed Control

    In Manual fan-control mode, the speed of the motor can be set in one of the following ways: • The manual (fixed) fan speed may be set via iCOM. • Remotely using a Liebert IntelliSlot® card. Vertiv | Liebert® iCOM™ Installer/User Guide |...
  • Page 43: Automatic Fan-Speed Control

    NOTE: Local adjustments to fan speed are overridden when remote/BMS fan-speed control is set. 3.1.9 Automatic Fan-speed Control Liebert iCOM on the CRV is factory-set for supply-air sensor control of fan speed and cooling capacity to ensure that the iCOM is delivering precise cooling to the cold aisle.
  • Page 44: Scheduling Condenser And Cooling-Unit Tasks

    Touch Cancel to discard the changes. Condenser Setback Task-properties options Disabled Day Selects specific days on which noise-reduction operation is disabled when the schedule is enabled. Interval 1 Start and finish time of day that noise-reduction operates. Vertiv | Liebert® iCOM™ Installer/User Guide |...
  • Page 45: Scheduling Condenser-Fan Reversal

    Condenser Fan-reversal Task-properties options Reverse Fans At Duration Length of time, in seconds, the fans are reversed. Reverse Fans Every Selects number of days between fan reversal. Reverse Fans Now Enables/Disables immediate fan reversal. Vertiv | Liebert® iCOM™ Installer/User Guide |...
  • Page 46: Scheduling "Sleep" Times For Thermal-Management Units

    3.3 Setting General Thermal-management Unit Options NOTE: Depending on the type of thermal-managment unit, included components, and control settings of your system, all of the options listed may not be available on your iCOM display. Vertiv | Liebert® iCOM™ Installer/User Guide |...
  • Page 47: Setting Miscellaneous Options

    K11 (WA Relay) and AL Relay Sets action of the alarm and warning relays. • Direct = Open when power is applied to the control. • Reverse = Closed when power is applied to the control. Vertiv | Liebert® iCOM™ Installer/User Guide |...
  • Page 48: Automatic Restart After Power Failure

    2. In the category column, touch Fan Settings. The FAN SETTINGS panel displays. 3. Make adjustments as needed and click Save. The option settings are updated. • Touch Cancel to discard the changes without saving. Vertiv | Liebert® iCOM™ Installer/User Guide |...
  • Page 49 Increases the rate at which the fan speed changes for a quicker reaction of fan speed at high temperatures. Fanspeed Reposition Delay Length of time before fan speed can decrease, allowing temperature to stabilize before the change occurs. Vertiv | Liebert® iCOM™ Installer/User Guide |...
  • Page 50: Setting Compressor Options

    2. In the category column, touch Compressor Settings. The COMPRESSOR SETTINGS panel displays. 3. Make adjustments as needed and click Save. The option settings are updated. • Touch Cancel to discard the changes without saving. Vertiv | Liebert® iCOM™ Installer/User Guide |...
  • Page 51 The OPTIONS SETUP panel opens. 2. In the category column, touch Compressor Settings. 3. Use the Ball Valve Setpoint Offset slider to select amount of pressure added to open the valve wider, and touch Save. Vertiv | Liebert® iCOM™ Installer/User Guide |...
  • Page 52: Setting Humidifier Options

    Humidifier Settings options Humidification System Enabled Enables/Disables group-wide (network-wide) humidification by the cooling units in the group. Once enabled at the system level, individual units may be enabled using the Humidification Enabled paramater. Vertiv | Liebert® iCOM™ Installer/User Guide |...
  • Page 53: Setting Dehumidification Options

    Capacity increase permitted during dehumidification. Dehumidification Enabled Enables/Disables whether or not the compressor/valve is used for dehumidification when humidity is above the setpoint. Dehum Timer Length of time, in minutes, the dehumidifier may operate. Vertiv | Liebert® iCOM™ Installer/User Guide |...
  • Page 54: Setting Water-Leak Detector Options

    NOTE: Depending on the type of thermal-managment unit, included components, and control settings of your system, all of the options listed may not be available on your iCOM display. Water Leak Detector settings options Water Detector Type of water-leak detector installed. Vertiv | Liebert® iCOM™ Installer/User Guide |...
  • Page 55: Managing Events: Alarms, Warnings And Messages

    Alarms & Events panel fields Property Lists groups of events, expanding displays the events in each group. See Enabling Events and Editing Event Settings on the next page. Type Event type. See Selecting Event Type and Setting Alarm/Warning Notification on page 57. Vertiv | Liebert® iCOM™ Installer/User Guide |...
  • Page 56: Enabling Events And Editing Event Settings

    NOTE: To edit the event type and notification, see Selecting Event Type and Setting Alarm/Warning Notification on the facing page. 3. Use the EDIT panel to adjust the settings for the selected event or group of events. Vertiv | Liebert® iCOM™ Installer/User Guide |...
  • Page 57: Selecting Event Type And Setting Alarm/Warning Notification

    Listed with a red status dot on the ALARMS panel, the LED flashes, and the audible alarm sounds. Alarm See Table 10.1 on page 91, Section Viewing Unit Alarms on page 21, and Section Enabling the Audible Alarm Notification on page 60. Vertiv | Liebert® iCOM™ Installer/User Guide |...
  • Page 58 Unit On HCB Not Connected No Connection w/Unit1 Unit 07 Disconnected Unit Shut Down Heat Rej SPD No Power Unit 08 Disconnected Water Under Floor Heat Rej VFD On-Off Key Disabled Unit 09 Disconnected Vertiv | Liebert® iCOM™ Installer/User Guide |...
  • Page 59 Table 4.3 Events specific to Liebert MC Condenser EVENT DESCRIPTION • The Liebert iCOM board cannot establish communication with the Liebert MC condenser board for 10 seconds consecutively. • Alarm notification displayed for the corresponding circuit. CAN GC 1 or 2 •...
  • Page 60: Enabling The Audible Alarm Notification

    Table 4.5 on page 62. 3. In Customer Input X Active When, select whether the input is active (triggers events) when Opened or Closed. 4. Once input(s) are set, touch Save. The customer-input settings are saved. Vertiv | Liebert® iCOM™ Installer/User Guide |...
  • Page 61 • Opened = events are triggered when the contacts across the corresponding RAD terminal strip are open. • Closed = events are triggered when the contacts across the corresponding RAD terminal strip are closed. Vertiv | Liebert® iCOM™ Installer/User Guide |...
  • Page 62: Your System

    Event + Activates COND PUMP-HIGH WATER event and locks-out the humidifier. Alarm L C PMP Event + Activates COND PUMP-HIGH WATER event and shuts-down the cooling unit. Alarm SD POWER A Event only. POWER B Event only. Vertiv | Liebert® iCOM™ Installer/User Guide |...
  • Page 63: U2U Networking

    Without a plan, adjacent units could be operating or inactive, which may not provide proper heat-load balance or efficient use of cooling capacity. Vertiv | Liebert® iCOM™ Installer/User Guide |...
  • Page 64: Configuring U2U Network Settings

    Troubleshooting Network-settings Issues on page 66. To configure unit-to-unit networking: On the Service menu, touch BMS & Teamwork Setup > U2U Setup. The U2U NETWORK SETTINGS panel opens. 2. Touch the field to edit. The keypad opens. Vertiv | Liebert® iCOM™ Installer/User Guide |...
  • Page 65 Network address of the display and control board. NOTE: Last 3 digits must be a unique value and need not be sequential. However, we recommend that they match the U2U address for easier reference later. Vertiv | Liebert® iCOM™ Installer/User Guide |...
  • Page 66: Troubleshooting Network-Settings Issues

    The button indicates the number of issues and also changes color when a problem exists, Table 5.1 below. Table 5.1 Issues-button status colors COLOR DESCRIPTION Green No problems. Number of issues is zero. Problem(s) detected. Number of issues displayed. Vertiv | Liebert® iCOM™ Installer/User Guide |...
  • Page 67: Modifying U2U Network Settings

    NOTE: Depending on the changes made, the Save button updates to indicate the components that need rebooted or restarted. If the control board reboots, the cooling unit suspends operation for 60 seconds, then resumes operating. Vertiv | Liebert® iCOM™ Installer/User Guide |...
  • Page 68 This page intentionally left blank. Vertiv | Liebert® iCOM™ Installer/User Guide |...
  • Page 69: Teamwork, Stand-By And Rotation For Cooling Units

    Teamwork mode is set. • Touch Cancel to discard changes. Figure 6.1 Teamwork icons ITEM DESCRIPTION No teamwork. Mode 1 - Parallel teamwork Mode 2 - Independent teamwork Mode 3 - Optimized aisle teamwork Vertiv | Liebert® iCOM™ Installer/User Guide |...
  • Page 70 Limits the fan speed of the group until all units in cascade are powered-on. Once all units are operating, the fan speed may increase beyond this setting. Number of Connected Units Number of units connected in the group if U2U networked. Vertiv | Liebert® iCOM™ Installer/User Guide |...
  • Page 71: No Teamwork-Multiple Zones In One Room

    In Teamwork mode 2, the setpoints for all units must be identical. The proportional band, deadband, and related settings may differ by unit. Fan speed is modulated per unit. Rotation and cascading is not available, so expect un-even distribution of work hours. Vertiv | Liebert® iCOM™ Installer/User Guide |...
  • Page 72: Teamwork Mode 3-Optimized-Aisle Operation

    On the Service menu, touch BMS & Teamwork Setup > Teamwork / Standby. The TEAMWORK/STANDBY panel opens. 2. Touch Standby. The STANDBY CONTROL panel displays. 3. Adjust the settings, then touch Save. • Touch Cancel to discard the changes. Vertiv | Liebert® iCOM™ Installer/User Guide |...
  • Page 73: Setting A Rotation Schedule

    1 operating. At rotation, unit 1 goes to stand-by and unit 4 activates, then 7, 10, 2, and so on. You can select 1 to 8 units in a single rotation schedule. Vertiv | Liebert® iCOM™ Installer/User Guide |...
  • Page 74: Manually Rotating The Operating And Stand-By Units

    2. On the Service menu, touch BMS & Teamwork Setup > Teamwork / Standby. The TEAMWORK/STANDBY panel opens. 3. Touch Unit Rotation. The UNIT ROTATION CONTROL panel displays. 4. Touch Rotate Now, then touch Save. The operating and stand-by units are rotated. Vertiv | Liebert® iCOM™ Installer/User Guide |...
  • Page 75: External Monitoring And Building-Management Systems

    7.1 Building Management Systems Operation Building-management system (BMS) includes disconnect fail-safe, manual fan-speed control, and the following communication settings: • Monitoring protocol • Monitoring address • BMS connection to fan control • BMS hand-shake timer Vertiv | Liebert® iCOM™ Installer/User Guide |...
  • Page 76: Adjusting Monitoring (Intellislot) Settings

    On the Service menu, touch BMS & Teamwork Setup > BMS Setup. The BMS SETUP panel opens. 2. Touch Control Settings. The CONTROLL SETTINGS secondary panel opens. 3. Adjust the settings, and touch Save. The settings are configured. Vertiv | Liebert® iCOM™ Installer/User Guide |...
  • Page 77 Currently-selected fan-control sensor. Must be set to “Manual” for BMS control. See Configuring fan setpoints. Handshake Sets time-period, in minutes, in which communication between the BMS and iCOM must occur. Maximum Fanspeed Current fan-speed setting (set via fan setpoints or by BMS). Vertiv | Liebert® iCOM™ Installer/User Guide |...
  • Page 78 This page intentionally left blank. Vertiv | Liebert® iCOM™ Installer/User Guide |...
  • Page 79: Configuring Auxiliary Devices

    On the Services menu, touch Auxiliary Device Setup > Sensors > Wired Remote Sensors > Setup. The set-up SENSOR PROPERTIES panel opens. 2. Adjust the settings for the cooling units sensor array, and touch Save. Wired-remote sensor—set-up options on the next page describes the setting options. Vertiv | Liebert® iCOM™ Installer/User Guide |...
  • Page 80 When Unit Remote Sensors Mode is Average, selects the number of sensors used to calculate the average temperature. • If the number selected is smaller than the number of REM Sensors set to Control, only the highest readings are used for the calculation. Vertiv | Liebert® iCOM™ Installer/User Guide |...
  • Page 81 Current reading of the right sensor probe. May be a temperature or humidity reading, depending on the connected sensor. Right Lead Offset Correction (calibration) value added to the reading. Used in the event that the sensor reading is incorrect. • May be a positive or negative value. Vertiv | Liebert® iCOM™ Installer/User Guide |...
  • Page 82 This page intentionally left blank. Vertiv | Liebert® iCOM™ Installer/User Guide |...
  • Page 83: Administering Firmware, Settings And Security

    It also includes settings to use while performing the upgrade. NOTE: Only personnel who have completed Vertiv™ training should perform a control-board update. The iCOM Service Tool (iST) is required to update control-board firmware. Contact technical support at 1-800-543-2778 for information on control-board updates.
  • Page 84 Drop-down selector right of the slash updates the control-board configuration. Options are: • No = default, no save or upload. • Save = save changes to the control-board settings. • Load = upload settings to the control board. Vertiv | Liebert® iCOM™ Installer/User Guide |...
  • Page 85 In the Lock for Upgrade field on the FIRMWARE UPGRADE PARAMETERS panel, select Unlock, then select Yes. 2. Touch Save. The changes are executed. Vertiv | Liebert® iCOM™ Installer/User Guide |...
  • Page 86: Managing Access Permission And Pins

    Use a back-up file to restore the unit settings in the event of a failure. On the Service menu, touch Backup & Security > Backup and Restore. The BACKUP & RESTORE panel opens. 2. Touch the Action Type drop-down, then Backup. Vertiv | Liebert® iCOM™ Installer/User Guide |...
  • Page 87: Restoring Settings

    Save a copy of the iCOM display settings for later import to another iCOM for identical display settings on both systems. On the Service menu, touch Backup & Security > Backup and Restore. The BACKUP & RESTORE panel opens. 2. Touch the Action Type drop-down, then Export. Vertiv | Liebert® iCOM™ Installer/User Guide |...
  • Page 88: Importing Settings

    2. Touch the Reset to Defaults button in the lower-right corner, then Continue on the confirmation dialog. (or Cancel to disregard the reset). The display restarts, and the start-up wizard opens to assist in configuring the reset display. Vertiv | Liebert® iCOM™ Installer/User Guide |...
  • Page 89: Configuring With The Start-Up Wizard

    4. Determine the use of network communications and configure as needed, then touch Next. The SUMMARY panel opens. 5. Review the selections and settings and, if correct, touch Finish. • If corrections are needed, touch Previous to return to the appropriate panels. Vertiv | Liebert® iCOM™ Installer/User Guide |...
  • Page 90 This page intentionally left blank. Vertiv | Liebert® iCOM™ Installer/User Guide |...
  • Page 91: Performing Diagnostics

    The MANUAL MODE confirmation dialog opens. 4. Touch OK to enable manual mode. Enable is checked and manual control for diagnostics enabled. • Touch Cancel to close the dialog and manual mode remains disabled. Vertiv | Liebert® iCOM™ Installer/User Guide |...
  • Page 92: Disabling Diagnostics Manual Mode

    Maximum fan speed during manual/diagnostic mode. Low Supply Temperature Counter Number of low-temperature alarm events. Fan Motors Enables/Disables fan motor during manual/diagnostic mode. Status Airflow 1/2 Status of Air Safety Switch: Open or Closed.. Vertiv | Liebert® iCOM™ Installer/User Guide |...
  • Page 93: Diagnosing Compressor-Circuit Issues

    Capacity at which compressor runs in manual mode. Compressor Mode Selects compressor operation during manual/diagnostics mode. Options are: • 0 = Run (normal operation) • 1 = Evacuate • 2 = Charge Compressor Overload Compress overload status. Vertiv | Liebert® iCOM™ Installer/User Guide |...
  • Page 94 • Non-zero = Low suction pressure condition. Low Pressure Status Status of compressor’s low-pressure switch. Refrigerant Leak Detection Enables/Disables detection during testing. Status HT1 Count of times compressor is powered-off for high scroll temperature. Vertiv | Liebert® iCOM™ Installer/User Guide |...
  • Page 95: Resetting High-Pressure Alarm Code

    NOTE: Depending on the type of thermal-managment unit, included components, and control settings of your system, all of the options listed may not be available on your iCOM display. Diagnostics—Humidifier options Humidifier Enables/Disables humidification in manual/diagnostic mode. Humidifier Drain Enables/Disables humidifier drain. Vertiv | Liebert® iCOM™ Installer/User Guide |...
  • Page 96: Diagnosing Digital-Output Issues

    Diagnostics—Digital-output options Alarm Relay Enables/Disables alarms during manual/diagnostic mode. Q15 Output State Enables/Disables Q15 output during manual/diagnostic mode. Vertiv | Liebert® iCOM™ Installer/User Guide |...
  • Page 97: Diagnosing Analog-Output Issues

    Diagnostics—Customer-input options Input N Status of customer-input sensors. (where “N” is the input number) Input N Description of customer-input sensors. (where “N” is the input number) Vertiv | Liebert® iCOM™ Installer/User Guide |...
  • Page 98: Diagnosing Dehumidifier Issues

    Diagnostics—Dehumidifier options 12h Dehum Counter Number of dehumidification-timer time-outs. Dehumidification Envelope Current status of dehumidification envelope. • Active = Dehumidification is disabled because the Dehum Timer has timed-out. Vertiv | Liebert® iCOM™ Installer/User Guide |...
  • Page 99: Managing Brown-Out Protection

    T FAN = top fan • HP = high pressure • LP = low pressure • EHO = heater-safety thermostat • B FAN = bottom fan Enable Brown Out Protection Enables/Disables brown-out protection during manual/diagnostic mode. Vertiv | Liebert® iCOM™ Installer/User Guide |...
  • Page 100 This page intentionally left blank. Vertiv | Liebert® iCOM™ Installer/User Guide |...
  • Page 101: Customizing Your Icom Display

    Time to elapse before display locks and dims. Language Selects the display language. LED Brightness Percentage brightness of the display. Measurement System Selects the units of measurement. Options are: • Imperial (°F) • Metric (°C) Vertiv | Liebert® iCOM™ Installer/User Guide |...
  • Page 102: Customizing Main-Display Views

    Table 11.1 on page 104, describes the content types. 7. When finished, touch Save. The view is saved. • Touch Cancel to exit without saving the view. 8. Touch Save. The PANEL CONTENT list is saved with the new view layout. Vertiv | Liebert® iCOM™ Installer/User Guide |...
  • Page 103: Editing A Display View Layout

    11.3.1 Accessing panel-edit mode NOTE: You must be logged-in to access the editing options. See Powering-on iCOM and Logging- in/Unlocking Controls on page 11. Touch the panel-edit icon, The Change Content button appears. Vertiv | Liebert® iCOM™ Installer/User Guide |...
  • Page 104: Replacing Panel Content

    11.3.3 Resizing and Moving a panel On the panel, touch , then touch again. The panel-edit options display, Figure 11.2 on the facing page: • Border with 8 handles for resizing • Blue “move” circle in the center Vertiv | Liebert® iCOM™ Installer/User Guide |...
  • Page 105: Removing A Panel

    Resizing and Moving a panel on the previous page. 3. Touch the parameter to add. Vertiv | Liebert® iCOM™ Installer/User Guide |...
  • Page 106: Moving Content In A Status Panel

    Once you know where they are, you’ll be able to find them in the categories on the Customize Labels panel. 2. Touch , then The User menu opens. Vertiv | Liebert® iCOM™ Installer/User Guide |...
  • Page 107 The label(s) are updated. Figure 11.4 on the next page shows the Analog Input Properties panel with the custom labels that replaced “Property” and “Value.” Figure 11.3 Custom text for the analog-input properties labels Vertiv | Liebert® iCOM™ Installer/User Guide |...
  • Page 108: Exporting, Importing And Customizing Labels Using A Text Editor

    NOTE: You must use an editor that interprets Linux line endings, otherwise all of the lines will run together. For example, Microsoft WordPad will interpret the Linux line endings, but Microsoft Notepad will not. analog_input/row_customer_analog_inputs=Unit A Inputs analog_input_properties/header_property=Property analog_input_properties/header_value=Value Vertiv | Liebert® iCOM™ Installer/User Guide |...
  • Page 109 USB port on the rear of the touchscreen display, then navigate to the Custom Labels panel and touch Import. 8. Locate the updated text file in the drop-down list, and touch Import. The dialog closes and the customizations display on the menus and panels that you updated. Vertiv | Liebert® iCOM™ Installer/User Guide |...
  • Page 110: Liebert Icom Hardware Installation

    12 LIEBERT ICOM HARDWARE INSTALLATION Your unit includes the Liebert iCOM controller. This section describes the installation of connections and cabling to fully utilize the iCOM features. 12.1 Installing Wired Remote Sensors Up to 10 remote-sensor modules, installed in the monitored racks and connected to the cooling unit, provide control and reference input to iCOM and building-management systems.
  • Page 111 If settings are incorrect, the control will not operate properly. The DIP switches in 2T sensors included with each Liebert iCOM are factory-set according to Table 11.3 below. If adding additional 2T sensors, use the steps that follow to set the DIP switches.
  • Page 112 The last 2T sensor in the array must be terminated. If more than the 3 factory-supplied sensors are installed, sensor #3 must be unterminated and the last sensor must be terminated. NOTE: Up is on, down is off on the DIP switch. Figure 11.7 DIP switches in 2T sensor Vertiv | Liebert® iCOM™ Installer/User Guide |...
  • Page 113: Terminating The Last Sensor On The Canbus Link

    3. Remove the black jumper from pins 1 and 2 on the P3 pin connector, and install it on pins 2 and 3 as shown in Figure 11.9 on the next page. 4. Replace the sensor cover. The 2T sensor is terminated in the CANbus link. Vertiv | Liebert® iCOM™ Installer/User Guide |...
  • Page 114: Routing Canbus Cable And Preparing For Sensor Installation

    See Preparing for sensor cabling of CRV 600-mm (24-in.) units—CR020, CR035 and CR040 on page 117. NOTE: Connecting the CANbus sensors requires entering the high-voltage electrical compartment in the unit. Consider hiring a certified electrician. Vertiv | Liebert® iCOM™ Installer/User Guide |...
  • Page 115 Figure 11.10 on the next page. • Route the cable through the low-voltage-access, 7/8-in. knockout using the proper strain relief. • Once inserted through knockout, route the cable to the IntelliSlot bracket inside the unit. Vertiv | Liebert® iCOM™ Installer/User Guide |...
  • Page 116 Top-entry field routing of CANbus wiring Top-entry field routing of low-voltage wiring CW unit Bottom-entry field routing of low-voltage and CANbus DX unit CANbus and low-voltage wiring route in DX unit Ground connector (factory installed) Vertiv | Liebert® iCOM™ Installer/User Guide |...
  • Page 117 5. At the top of the cabinet, route the cable through the 7/8-in. knockout using the proper strain relief, then route the cable to the return-air temperature sensor inside the unit, Figure 11.12 on the next page. Vertiv | Liebert® iCOM™ Installer/User Guide |...
  • Page 118 Figure 11.12 CANbus top-entry wiring for CRV 600-mm (24-in.) units—CR020, CR035, and CR040 ITEM DESCRIPTION Top/Display door Cable-connection top entry Temperature sensor Rear view Front view Vertiv | Liebert® iCOM™ Installer/User Guide |...
  • Page 119: Installing 2T Sensors In The Racks To Monitor

    Figure 11.13 Remove Termination plug and insert CAN cable ITEM DESCRIPTION Termination plug CAN cable 12.1.4 Installing 2T sensors in the racks to monitor Tools required • Medium, flat-head screw driver to open electric-panel dead-front • Cutting tool to trim cable ties Vertiv | Liebert® iCOM™ Installer/User Guide |...
  • Page 120 First probe, 12 in. (305 mm) from top Second probe, in approximate center of rack and in front of the equipment 2T sensors with labels visible Cable-connection top entry point (use a field-supplied and field-installed protective bushing) Vertiv | Liebert® iCOM™ Installer/User Guide |...
  • Page 121 Cable-connection top entry point. Use a field-supplied and field-installed protective bushing. Cable-connect bottom entry, refer to Preparing for sensor-cabling of CRV 300 -mm (12-in.) units—CR019 and CR032 on page 115, and use a field-supplied and field-installed protective bushing. Vertiv | Liebert® iCOM™ Installer/User Guide |...
  • Page 122: Connect The Canbus Cable And Ground

    For cable up to 150-ft (45-m) long, no special considerations are needed. • Cable 150 ft (45 m) to • 300 ft (91 m), contact the factory. • The CANbus cable network requires a ground wire. Vertiv | Liebert® iCOM™ Installer/User Guide |...
  • Page 123: Installing The U2U Network

    Network switch • IEEE 802.3; IEEE 802.3u • 10/100 Mbps speed • Multiple 10/100 RJ-45 ports, one shared. • RJ-45 up-link port NOTE: Up to 32 cooling units may be connected in a U2U network. Vertiv | Liebert® iCOM™ Installer/User Guide |...
  • Page 124: Plan Wiring Runs

    Before you begin, refer to Preparing for U2U Group Set-up, and Configuring U2U Network Settings. – or – Contact Vertiv™ Technical Support at 1-800-543-2778 or https://www.vertivco.com/en- us/support/. U2U Network Requirements The network must be private: •...
  • Page 125: Wiring Cooling Units Without Wall-Mount Displays

    NOTE: Cooling units are factory-wired for stand-alone operation. Do not connect the U2U network cabling before setting the U2U network configuration/groups. Network communication conflicts and un-reliable display readings will result. NOTE: Before you begin, refer to Preparing for U2U Group Set-up, and Configuring U2U Network Settings. Vertiv | Liebert® iCOM™ Installer/User Guide |...
  • Page 126 Figure 11.17 Connecting 300 mm (12 in.) units ITEM DESCRIPTION Touchscreen (rear view) Ethernet cable (factory-supplied) Coupler (factory-supplied) Straight-through Ethernet cables Network switch (field-supplied) to ETH-2 on rear of other cooling-unit touchscreeens iCOM I/O board Vertiv | Liebert® iCOM™ Installer/User Guide |...
  • Page 127 Figure 11.18 below. Figure 11.18 Connecting 600 mm (24 in.) units ITEM DESCRIPTION Touchscreen (rear view) Ethernet cable (field-supplied) Ethernet cable (factory-supplied) iCOM I/O board Network switch (field-supplied) to ETH-2 on rear of other cooling-unit touchscreeens Vertiv | Liebert® iCOM™ Installer/User Guide |...
  • Page 128: Wiring Cooling Units With Wall-Mount Displays

    To connect wiring: On each wall-mount display (32 max.), connect one plug of a straight-through Ethernet cable to port P64 on the rear of the display. 2. Connect the other end to the U2U network switch. Vertiv | Liebert® iCOM™ Installer/User Guide |...
  • Page 129: Appendices

    Via Leonardo Da Vinci 8 Zona Industriale Tognana 35028 Piove Di Sacco (PD) Italy +39 049 9719 111 Fax: +39 049 5841 257 Asia 7/F, Dah Sing Financial Centre 3108 Gloucester Road, Wanchai Hong Kong 852 2572220 Fax: 852 28029250 Vertiv | Liebert® iCOM™ Installer/User Guide |...
  • Page 130 This page intentionally left blank. Vertiv | Liebert® iCOM™ Installer/User Guide |...
  • Page 132 VertivCo.com | Vertiv Headquarters, 1050 Dearborn Drive, Columbus, OH, 43085, USA © 2017 Vertiv Co. All rights reserved. Vertiv and the Vertiv logo are trademarks or registered trademarks of Vertiv Co. All other names and logos referred to are trade names, trademarks or registered trademarks of their respective owners. While every precaution has been taken to ensure accuracy and completeness herein, Vertiv Co.