NetSure™ Rectifier Module User Manual (UM1R243000 / 11BJ1307WA), Revision G Specification Number: 1R242500, 1R243000 Model Number: R24-2500, R24-3000...
Page 2
This document may contain confidential and/or proprietary information of Vertiv Group Corporation, and its receipt or possession does not convey any right to reproduce, disclose its contents, or to manufacture or sell anything that it may describe.
SAFETY! Informs the reader of general safety information, reminders, precautions, or policies not related to a particular source of hazard or to fire safety. (ISO, ANSI, OSHA) Vertiv | NetSure Rectifier Module User Manual (UM1R243000 / 11BJ1307WA) | Rev. G...
ALERT! Installation or removal of equipment containing static sensitive components requires careful handling. Before handling any equipment containing static sensitive components, read and follow the instructions contained on the Static Warning Page. Vertiv | NetSure Rectifier Module User Manual (UM1R243000 / 11BJ1307WA) | Rev. G...
If necessary to repair equipment containing static sensitive components, wear an appropriately grounded wrist strap, work on a conductive surface, use a grounded soldering iron, and use grounded test equipment. Vertiv | NetSure Rectifier Module User Manual (UM1R243000 / 11BJ1307WA) | Rev. G...
• Power (One Rectifier Module): 2500W or 3000W at Vout ≥24VDC. • Output Characteristics: The relationship between output voltage and current is depicted graphically in the following illustrations. Vertiv | NetSure Rectifier Module User Manual (UM1R243000 / 11BJ1307WA) | Rev. G...
Page 8
80% of full rated power at +65°C (149°F). Full power capability is restored when the temperature decreases to below approximately +50°C (+122°F). Refer to the following curve illustrating typical operating parameters. Vertiv | NetSure Rectifier Module User Manual (UM1R243000 / 11BJ1307WA) | Rev. G...
• Inrush Current: Peak does not exceed 2 times the RMS input current at full load, nominal input voltage, and for any duration of AC input interrupts. Under the above conditions, standard AC distribution circuit breakers will not trip. Vertiv | NetSure Rectifier Module User Manual (UM1R243000 / 11BJ1307WA) | Rev. G...
Page 10
Maximum Input Current: 15.43A at 100% of full load with output adjusted to 28.5 volts DC as measured at the shelf output terminals, and input voltage of 180 volts. Vertiv | NetSure Rectifier Module User Manual (UM1R243000 / 11BJ1307WA) | Rev. G...
3°C per 1000 feet above 5000 feet. • Surge Protection: Compliance with EN61000-4-5 Installation Class 4, and capable of withstanding surges per ANSI/IEEE C 62.41 1980 Category B3 across the input terminals. Vertiv | NetSure Rectifier Module User Manual (UM1R243000 / 11BJ1307WA) | Rev. G...
No. 60950-00 and is tested and Certified by UL ("c UR") as a Component Type Power Supply. • The rectifier is RoHS 5/6 compliant. • NEBS Compliance (when used in a compliant system): Compliance verified by a Nationally Recognized Testing Laboratory (NRTL) per GR-1089-CORE and GR-63-CORE. Contact Vertiv for NEBS compliance reports. Standard Features •...
Page 13
HVSD restart timer starts (time value configurable via the controller, factory default is 5 minutes). If output voltage again exceeds the high voltage shutdown value before Vertiv | NetSure Rectifier Module User Manual (UM1R243000 / 11BJ1307WA) | Rev. G...
Page 14
For example, a higher temperature or output power increases the fan speed. Fan speed control can be disabled by the controller. Vertiv | NetSure Rectifier Module User Manual (UM1R243000 / 11BJ1307WA) | Rev. G...
• Dimensions (H x W x D): 1.63” (41.4mm) x 4.88” (124mm) x 14.96” (380mm). • Local Controls: None. • Local Status and Alarm Indicators: Power (Green) Protection (Yellow) Alarm (Red) Vertiv | NetSure Rectifier Module User Manual (UM1R243000 / 11BJ1307WA) | Rev. G...
Turn the power to the rectifier off or remove the rectifier, wait 30 seconds or more (until the LEDs on the rectifier extinguish), then turn the power to the rectifier on or re-insert the rectifier. Vertiv | NetSure Rectifier Module User Manual (UM1R243000 / 11BJ1307WA) | Rev. G...
Page 17
Rectifier output disabled for any reason, including overvoltage shutdown and internal output fuse Alarm open. (Red) Rectifier addresses contradictory. One or both fans not operating Flashing (rectifier shuts down). Vertiv | NetSure Rectifier Module User Manual (UM1R243000 / 11BJ1307WA) | Rev. G...
Refer to the Power System documentation for instructions. Figure 2: Rectifier Module Handle/Latch Mechanism Note: Handle must be open when installing or removing module. Screw Handle in Closed Position Vertiv | NetSure Rectifier Module User Manual (UM1R243000 / 11BJ1307WA) | Rev. G...
Verify that the Rectifiers are operating normally. Enable the external alarms, or notify appropriate personnel that this procedure is finished. Ensure that there are no local or remote alarms active on the system. Vertiv | NetSure Rectifier Module User Manual (UM1R243000 / 11BJ1307WA) | Rev. G...
Reinstall the rectifier and again check for proper airflow. Enable the external alarms, or notify appropriate personnel that this procedure is finished. Ensure that there are no local or remote alarms active on the system. Vertiv | NetSure Rectifier Module User Manual (UM1R243000 / 11BJ1307WA) | Rev. G...
Page 23
Fan Power Connectors Faceplate Mounting Screws (4) Align holes in fan with tabs on faceplate. Position fans so that power cables exit fans here. Fans Faceplate Front View Vertiv | NetSure Rectifier Module User Manual (UM1R243000 / 11BJ1307WA) | Rev. G...