Table 13:
Exchange of Information between Rectifier and Controller
Commands / signals that can be
received by the Rectifier from the
Controller.
• Turn On/Off
• Current Walk-in On/Off
• HVSD (High Voltage Shutdown)
Reset
• Current Limit Adjustment
• Voltage Regulation
• External Control Circuits: Provided via the associated controller. Refer to the separate Power System
documentation for a complete description of available external control circuits.
• External Alarm Circuits: Provided via the associated controller. Refer to the separate Power System
documentation for a description of available external alarms.

Mechanical Specifications

• Dimensions:
a)
Millimeters: 86.0 (Height) X 84.5 (Width) X 272.0 (Depth)
b)
Inches: 3.4 (Height) X 3.3 (Width) X 10.7 (Depth)
• Weight: 2.4 kg (5.3 lbs).
Vertiv
| NetSure Rectifier Module User Manual (UM1R482000e / 11BU1360YY) | Rev. J
Information gathered by the
Controller from the Rectifier.
• Input Voltage
• Output Voltage
• Output Current
• Current Limit Setting
• Temperature
• Over Voltage Setting
• On/Off Status
• Fault Alarms, such as:
HVSD
Fan Fail
• Protection Alarms, such as:
Input Voltage Protection
Inner DC Bus Voltage Protection
High Temperature Protection
• Thermal Derating
• AC Derating
• AC Fail
• Imbalance Output Current
• Address
• Code
• Date
• Software Version
• Hardware Version
23