Service
5.1.4

Remote monitoring

A Remote Monitoring E-mail function has been introduced in UniSAB III. This function enables UniSAB
III to report compressor operation and events i.e. trend files, shutdowns and alarms for central remote
monitoring.
This picture shows the set-up parameters for Remote Monitoring. Remote monitoring must be set to Yes
to enable Trend and Events to the remote monitor server.
Note: Before Remote mon. can be configured to Yes the Remote monitoring functionality must have
been previously activated. See subsection 6.6.5 Function interface.
No.
Remote monitoring
1
Retries
2
(max. no of monitor and user mail retries)
Port (SMTP port no.)
3
4
Heartbeat
Alarm
5
(enable Alarm info to remote monitoring)
Max. hour
6
(max. no. of event mails per hour)
Last e-mail
7
(status information for last sent e-mail)
Last e-mail status
Nothing sent
Success
Invalid Sender
Invalid Recipient
No connection
DNS error
Authentication method
Authentication failed
Discarded
Engineering manual - UniSAB III 1.10.8
001930 en 2021.06
Service/Remote monitoring
Function
No e-mail has been dispatched.
Last e-mail transmission was OK.
UniSAB III e-mail settings are not correct.
Recipients e-mail settings are not correct.
It is not possible to establish connection to e-mail server.
DNS server IP address is not correct or the server is not available.
Connection was rejected because UniSAB III did not support the re-
quested e-mail server authentication method.
Connection to e-mail server was rejected during the authentication
session.
Last e-mail transmission has been interrupted during dispatch and the
number of Retries was exceeded.
The cause is probably a bad or unstable connection to e-mail server.
169/346
Use
Choices
1/2 No, Yes
1/2 3, [1-10]
1/2 25, [1-32000]
1/2 4, [1-24]
1/2 No, Yes
30, [1-120]
With the default setting 30, the minimum
1/2
time to elapse between two consecutive
event mails will be 60/30 = 2 minutes.
Nothing sent, Success, Invalid Sender, In-
valid recipient, No connection, DNS error,
1/2
Authentication method, Authentication
failed, Discarded