Compressor control and surveillance
Alarm surveillance
During start the following alarms are delayed:
Low oil pressure
High filter diff. pressure
Low superheat
High superheat
Low/high oil temperature
The delayed alarms are described in section 6.5 Timers.
3.3.14

GST with oil pump

The compressors are equipped with capacity slide and automatic Vi-control. The Vi is controlled in three
steps.
The oil pump is used to maintain a minimum oil pressure level during operation and to return the ca-
pacity slide to minimum position before the compressor is started. During operation, the oil pump is
started and stopped in accordance with the compressor differential pressure.
The difference is set in the picture Oil/Pressure/Control whereupon Set point 1 and Set point 2 will ap-
pear. Set point 1 is the pump start pressure and Set point 2 is the pump stop pressure. Therefore, Set
point 1 must be set at the lowest pressure level.
Move the cursor to Set point 1, press
value and press
to store the value.
Adjust Setpoint 2 the same way.
If the compressor differential pressure is below Set point 1 during operation, the pump will start
immediately.
When the compressor differential pressure has been higher than Set point 2 for 60 seconds, the pump
will stop.
Starting sequence
When the compressor has received starting permission, UniSAB III will check if the capacity slide is in
minimum position. If the capacity slide is higher than 5% position the solenoid valve for decreasing the
capacity slide position is activated. If the capacity slide is still higher than 5% position, an Oil log error
shutdown will be issued and the compressor will not start. If the capacity slide is lower than 5% the com-
pressor is allowed to start.
Before start-up UniSAB III will also check the oil level. If the oil level is too low an oil system error alarm
will be issued. No signal from the oil level switch during operation will result in shutdown after a delay of
30 seconds.
If the oil temperature is lower than the set limits, a low oil separator temp alarm or shutdown will be is-
sued. The limits for oil separator temperature can be set in the menu Control values/Oil/Separator temp/
Limits.
If the oil level switch is active, the compressor will start. If the differential pressure is lower than Set point
1, the oil pump will also start. When the compressor differential pressure has been higher than Set point
2 for 60 seconds, the pump will stop.
If the differential pressure is higher than Set point 1 when the compressor is started, the oil pump will not
start.
Engineering manual - UniSAB III 1.10.8
001930 en 2021.06
45 sec.
300 sec.
300 sec.
300 sec.
300 sec.
to enter the parameter change field, use
109/346
and
to adjust the