Download Print this page

Beretta Ciao X Installer And User Manual page 25

Hide thumbs Also See for Ciao X:

Advertisement

Available languages
  • EN

Available languages

  • ENGLISH, page 20
b
"Straight length" means free of bends, and includes terminals and
joints.
b
The boiler is supplied without the flue gas exhaust/air suction kit,
since it is possible to use the accessories for condensing applian-
ces that best fit the installation characteristics (see catalogue).
b
To ensure greater installation safety, fix the pipes to the wall
(wall or ceiling) using special fixing brackets to be positioned
at each joint, at a distance such as not to exceed the length of
each individual extension and immediately before and after each
change of direction (bend).
b
The maximum lengths of the pipes refer to the flue accessories
available in the catalogue.
b
It is compulsory to use specific pipes.
b
The non insulated flue gas outlet pipes are potential sources of
danger.
b
The use of a longer pipe causes a loss of output of the boiler.
b
The exhaust pipes can face in the direction most suited to the
installation requirements.
b
As envisaged by current legislation, the boiler is designed to take
in and dispose of flue gas condensate and/or meteoric water con-
densate deriving from the flue gas discharge system using its own
siphon.
b
If a condensate relaunch pump is installed, check the technical
data (provided by the manufacturer) regarding output, to ensure
it operates correctly.
- Position the discharge pipe so that the connection sits fully up against
the flue gases turret of the boiler.
- After positioning it, make sure the 4 notches (A) slip into the groove
(B).
- Fully tighten the screws (C) that hold the two flange locking terminals,
so the bend itself is restrained held in place.
B23P-B53P Ø60-100
Ø80-80
B
B
A
C
b
If the Ø 60-100 to Ø 80-80 splitter kit is used instead of the twin
pipe system, there is a loss in the maximum lengths as shown in
the table.
Loss of length (m)
Twin pipes with Ø 80 pipework (Ø50 - Ø60 - Ø80)
Thanks to the boiler characteristics, a Ø80 flue gas exhaust pipe can be
connected to the Ø50 - Ø60 - Ø80 piping ranges.
b
For the pipe, you are advised to make a project calculation in order
to respect the relevant regulations in force.
The table shows the standard configurations allowed.
Air suction
Flue gas
Reduction from Ø80 to Ø50 from Ø80 to Ø60
discharge
Flue base bend 90°, Ø50 or Ø60 or Ø80
For ducting pipe lengths see table
Ø80-125
B
A
B
Ø 50
Ø 60
Ø 80
5,5 for flue gases pipe
0,5
1,2
7,5 for air pipe
1 bend 90° Ø 80
4.5m pipe Ø80
1 bend 90° Ø 80
4.5m pipe Ø80
The boilers are factory set to:
Should greater lengths be required, compensate the pressure drop with
an increase in the r.p.m.of the fan, as shown in the adjustments table,
to provide the rated heat input, referring to paragraph "4.9 Adjustments".
b
The minimum calibration should not be modified.
b
In case of new fan speed adjustment, carry out the CO
procedure as indicated in paragraph "4.8 Combustion analysis".
Adjustment tables INSIDE CHIMNEY PIPES
Fan rotations rpm
CH
DHW
5.600
8.700
5.700
8.800
5.800
8.900
5.900
9.000
6.000
9.100
6.100
9.200
6.200
9.300
6.300
9.400
7.000
8.700
7.100
8.800
7.200
8.900
7.300
9.000
7.400
9.100
7.500
9.200
7.600
9.300
7.700
9.400
(*) Maximum length that can be installed ONLY with class H1 discharge pipes.
B
Fan rotations rpm
CH
DHW
5.600
8.700
5.700
8.800
5.800
8.900
5.900
9.000
6.000
9.100
C
6.100
9.200
6.200
9.300
6.300
9.400
7.000
8.700
7.100
8.800
7.200
8.900
7.300
9.000
7.400
9.100
7.500
9.200
7.600
9.300
7.700
9.400
(*)
Maximum length that can be installed ONLY with class H1 discharge pipes.
The Ø50 or Ø60 or Ø80 configurations contain Lab test data. In the event
of installations that differ from the indications in the "standard configu-
rations" and "adjustments" tables, refer to the equivalent linear lengths
below.
b
In any case, the maximum lengths declared in the booklet are gua-
ranteed, and it is essential not to exceed them.
COMPONENT
Bend 45°
Bend 90°
Extension 0.5m
Extension 1.0m
Extension 2.0m
3.9
Installation on collective flues in positive
pressure
The collective flue is a flue gas exhaust system suitable for collecting
and expelling the combustion products of several appliances installed on
several floors of a building.
25
CH rpm
DHW rpm
max length pipes (m)
Ø50
6
5.600
8.700
1
6
7.000
8.700
1
twin flue pipe
Pipes Ø50
Pipes Ø60
Pipes Ø80
Maximum length (m)
6
19
95
12 *
33 *
165 *
16 *
39 *
195 *
19 *
46 *
230 *
23 *
53 *
265 *
27 *
61 *
305 *
29 *
67 *
335 *
32 *
73 *
365 *
6
19
95
12 *
33 *
165 *
16 *
39 *
195 *
19 *
46 *
230 *
23 *
53 *
265 *
27 *
61 *
305 *
29 *
67 *
335 *
32 *
73 *
365 *
compact twin flue pipe
Pipes Ø50
Pipes Ø60
Pipes Ø80
Maximum length (m)
1
9
45
7 *
23 *
115 *
11 *
29 *
145 *
14 *
36 *
180 *
18 *
43 *
215 *
22 *
51 *
255 *
24 *
57 *
285 *
27 *
63 *
315 *
1
9
45
7 *
23 *
115 *
11 *
29 *
145 *
14 *
36 *
180 *
18 *
43 *
215 *
22 *
51 *
255 *
24 *
57 *
285 *
27 *
63 *
315 *
Linear equivalent in metres Ø80 (m)
Ø 50
12,3
19,6
6,1
13,5
29,5
EN
Ø60
Ø80
19
95
9
45
19
95
9
45
check
2
∆P at boiler outlet
180
260
300
342
383
431
465
500
180
260
300
342
383
431
465
500
∆P at boiler outlet
180
260
300
342
383
431
465
500
180
260
300
342
383
431
465
500
Ø 60
5
8
2,5
5,5
12

Advertisement

loading