SPECIFICATIONS OF CONTROLLER

Power supply
Power consumption
Current consumption
Ambient temperature
Storage temperature
Humidity
Dimensions
Degree of protection
Fire class
Weight

SYSTEM OVERVIEW

Overview of Hardware

feature
RS485-1, isolated; for BACnet MS/TP, Panel Bus
RS485-2, non-isolated; for BACnet MS/TP, Panel Bus
Ethernet / RJ45 socket (for e-mailing, browser access, BACnet IP comm., etc.)
bus interfaces
USB 2.0 Device Interface (as Network Interface)
USB 2.0 Host Interface (max. 500 mA)
RS232 M-Bus communication via PW3 / PW20 / PW60 converters
power LED (green)
status LED (red, controllable by firmware)
LEDs
LED L1 (yellow)
LED L2 (yellow)
bus status LEDs (for isolated RS485-1 interface)
Socket for
RJ45 socket for connection of CLEAHMI21 External HMI (supported in future releases)
CLEAHMI21
(1)
Depending upon baud rate. For max. cable lengths, see section "RS485 Standard" on pg. 8. In the case of the Panel Bus, see also section
"Panel Bus Considerations" on pg. 15. In the case of the BACnet MS/TP Bus, see also section "BACnet MS/TP Bus Considerations" on pg. 20.
In the case of the Modbus, see also section "Modbus Considerations" on pg. 23.
(2)
Depending upon baud rate. See also section "M-Bus Considerations" on pg. 25.
NOTE:
The communication protocols listed here are only examples. The RS485-1 and RS485-2 interfaces also support
Modbus RTU Slave communication, as well as any RS485-based driver available within the Niagara Ecosystem.
EAGLEHAWK CONTROLLER – INSTALLATION & COMMISSIONING INSTRUCTIONS
Table 2. EAGLEHAWK specifications
19 ... 29 VAC, 50/60 Hz or
20 ... 30 VDC
typically dc: 5 W; max. 6 W
typically ac: 9 VA; max. 11 VA
typically dc: 210 mA; max. 240 mA
typically ac: 370 mA; max. 410 mA
0 ... 40 °C (wall-mounting)
0 ... 50 °C (cabinet/door mounting)
-20 ... +70 °C
5 ... 95% r.h. non-condensing
See Fig. 17 and Fig. 18.
IP20 (mounted on walls, with two accessory MVC-80-AC1 covers)
IP30 (mounted in cabinet doors, with accessory MVC-80-AC2)
V0
0.6 kg (excl. packaging)
Table 3. Overview of hardware
description
(1)
, Modbus RTU Master comm., etc.
(1)
, Modbus RTU Master comm., etc.
3
max. cable length
no.
(1)
1200 m
1
(1)
1
1200 m
1
100 m
3 m
1
3 m
1
(2)
1
1000 m
--
1
--
1
--
1
--
1
--
2
1
5 m
EN1Z-1005GE51 R0216