Dimensions and Mounting
Mounting the Standard Panel
Notes
• Surface mount indoors
• See panel weights below. Reinforce wall
structure for weight and local codes
• Ambient temperature: 32 °F-104 °F
(0 °C-40 °C)
• Relative humidity:
< 90% non-condensing
• Mount panel where audible noise is
acceptable (internal relays click)
• Mount panel within 7° of vertical
• Lutron recommends 1/4 in. (6 mm)
mounting bolts
• Cover overhangs enclosure by 3/4 in.
(19 mm)
Panel Weights
Model

DMWP12-FT

DMWP18-FT

DMWP24-FT

DMWP12-1204ML-20

DMWP18-1204ML-20

DMWP12-2774ML-20

8
Installation Guide for Lighting Zone Controllers
(continued)
Side View
Approximate Weight
113 lb. (51.3 kg)
120 lb. (54.4 kg)
127 lb. (57.6 kg)
127 lb. (57.6 kg)
135 lb. (61.2 kg)
150 lb. (68.0 kg)
This page applies to:
Front View
Input feeds
(feed-through
panel only),
switch legs, and
dimmed legs to
PELV (Class 2:
USA) wiring
Preferred feed wiring
(panel with main lugs
only)
Std.
Panel
loads
R