Installing Wall Controls
MW-V Wiring Instructions
Turn power OFF to the LZC or LZC panel before
connecting wall controls.
• Lights can be dimmed or switched ON/OFF from the
MW-V
• Lights can be switched ON/OFF to the MW-V preset
level from the VETS-P
VETS-P
Blue
Blue
LUTRON
Maximum of 9
VETS-P controls
LZC1 Connections
R
100-277 V
50/60 Hz
Coopersburg, PA 18036 USA
R
16 A Max.
Coopersburg, PA 18036 USA
DMW-LZC1
www.lutron.com
R
Lighting Zone Controller
®
Controlador de zona de luz
DMW-LZC1
Contrôleur de zone d'Éclairage
Lighting Zone Controller
LISTED
Controlador de zona de luz
Energy Management
Contrôleur de zone d'Éclairage
Equipment 5C81
For installation, refer to
Para la instalación,
Pour installation, référer au
the Digital microWATT
consulte la Guía del
guide pour quincaillerie
For installation, refer
Para la instalación, consulte
Pour installation, référer au
Hardware Installer's
Instalador de Digital
Digital microWATT
to the Lighting Zone
la Guía del Instalador de
guide Contrôleur de zone
Guide (p/n 031-268).
Controller Installer's Guide
Controlador de zona de luz
microWATT Hardware
(p/n 031-268) de
d'Éclairage de l'installateur
(p/n 031-268).
(p/n 031-268).
(p/n 031-268).
l'installateur.
(p/n 031-268).
1-800-523-9466
TEL
USA, Canada
FAX
Mexico
1-800-523-9466
1-888-235-2910
1-610-282-0298
USA, Canada
www.lutron.com
Mexico
1-888-235-2910
1-610-282-1243
www.lutron.com
Digital Link
®
Enlace Digital
LZC LINK
ADDR
LUTRON
LUTRON
Lien Digital
1
2
3
4
5
6
7
8
9
10
11 12 13 14 15
1
2
3
4
5
6
7
8
9
10
11 12 13 14 15
P/N 500-9066 Rev. F
P/N 500-9066 Rev. F
CLASS 2 LOW VOL
T AGE WIRING
1 2 3 4 5 6 7 8 9 10
To wall controls
VETS-P
Blue
Blue
LUTRON
To wall controls
Note:
+24 V signal is made only to
the first LZC if wall controls
are wired to multiple LZCs.
Do not connect +24 V
connections together on
multiple LZCs. Instead, CIR
COM must be connected
together.
R
• Wire size #18 AWG (1.0 mm
• Maximum wire length is 250 ft. (76 m)
• Wall controls are PELV (Class 2: USA) devices. Do
nut run their wires in the same conduit as line
voltage.
MW-V or
MW-VETS
LUTRON
Terminal
block on
back of
MW-V
Small Panel Connections
+24 V
PS Signal
PS Common
Circuit Common
WC Common
WC Signal
+24 V
+15 V
OCC Signal
OCC Common
Standard Panel Connections
1
4
7
2
5
8
3
6
9
To wall controls
3: CIR COM
4: WC COM
5: WC SIGNAL
6: +24 V
Installation Guide for Lighting Zone Controllers
This page applies to:
Small
Std.
Panel
Panel
LZC1
2
)
To WC COM
To WC SIGNAL
To +24 V
To CIR COM
To additional LZCs
(total of 3 LZCs
maximum)
+24 V
PS Signal
PS Common
Circuit Common
WC Common
WC Signal
+24 V
+15 V
OCC Signal
OCC Common
21