Lutron Electronics DMW-LZC1 Installation And Maintenance Manual page 11

Lighting zone controller and lighting zone controller panels

Advertisement

Wiring
(continued)
Small Panels: Conduit Entry
Danger! Locate and lock the supply breaker in
the OFF position, or remove the supply fuse
before continuing.
Small Panel with Main Lugs
PELV
(Class 2:
USA)
wiring only
Notes: Small Panel with Main Lugs
• Feed wiring (mains voltage wiring):
#10-#14 AWG (6.0-2.5 mm
• Small panels with main lugs accept one
15 or 20 A feed
- Total load is 16 A maximum
- Maximum rated load per circuit is 16 A
Preferred feed wiring
entry
Switch legs and
dimmed legs to
loads
2
)
R
Small Feed-Through Panel
Ground/earth
connection
PELV
(Class 2:
USA)
wiring only
Notes: Small Feed-Through Panel
• Feed wiring (mains voltage wiring):
#10-#14 AWG (6.0-2.5 mm
• Small feed-through panels accept four separate
15 or 20 A feeds
- Total load is 64 A maximum
- Maximum rated load per circuit is 16 A
Installation Guide for Lighting Zone Controllers
This page applies to:
Small
Panel
Feed wiring
from distribution
panel (typical
for all circuits)
Switch legs and
dimmed legs to
loads
2
)
11