Appendix: Voltage Map
Fixture Voltage Map
Where to Measure
Dimmed hot (orange)
to neutral (white)
Hot (black) to neutral
Blue to blue
Red to red
Yellow to yellow
Blue/white to
blue/white
Danger! Readings must be done while the circuit
is energized. Apply the voltage only to the meter.
Danger! Do not measure from one colored lamp
wire to another colored lamp wire (such as from
Red to Blue). This could exceed the voltage rating
of your meter.
Lighting Zone Controller Voltage Map
+24V
Occupant Sensor ON
21-26 V
Occupant Sensor OFF 21-26 V
Wall control ON
21-26 V
Wall control OFF
21-26 V
Emergency closed
21-26 V
Emergency open
21-26 V
36
Installation Guide for Lighting Zone Controllers
Voltage
(use True RMS Voltmeter)
Without lamp
With lamp
Low end: 0.70 x line voltage
High end: 0.98 x line voltage
Line Voltage +/- 10%
4 to 8 V
3 to 5 V
4 to 8 V
3 to 5 V
4 to 8 V
3 to 5 V
4 to 8 V
3 to 5 V
Terminal
WC Sig
+15V
14.1-16.2 V
14.1-16.2 V
1-26 V
14.1-16.2 V
<1 V
14.1-16.2 V
14.1-16.2 V
14.1-16.2 V
Set the meter to DC Volts.
Use the appropriate scale for
the voltage readings.
True RMS
Voltmeter
Occ Sig
EMERG
<2 or >10 V
5-7 V
0-7 V
21-26.6 V
Common (black lead) of
meter to circuit common
This page applies to:
Small
Panel
LZC1
3 -wire
dimming ballast
Dimmed hot (orange)
Hot (black)
Neutral (white)
Set the meter to AC Volts.
Use the highest scale for the
line voltage readings.
Use the 20 V
filament voltage readings.
Note: When measuring
voltages, keep the meter
body away from the lamps.
R
Coopersburg, PA 18036 USA
www.lutron.com
DMW-LZC1
Lighting Zone Controller
Controlador de zona de luz
Contrôleur de zone d'Éclairage
Para la instalación, consulte
For installation, refer
to the Lighting Zone
la Guía del Instalador de
Controller Installer's Guide
Controlador de zona de luz
(p/n 031-268).
(p/n 031-268).
USA, Canada
1-800-523-9466
Mexico
1-888-235-2910
®
1
2
3
4
5
6
7
8
9
10
PELV (Class 2: USA)
Touch red lead to
wiring
other terminals
Std.
Panel
Ground to fixture case
(green)
scale for the
100-277 V
50/60 Hz
16 A Max.
®