Lutron Electronics DMW-LZC1 Installation And Maintenance Manual page 29

Lighting zone controller and lighting zone controller panels

Advertisement

Appendix: Wiring Load Interfaces
Incandescent Load and Control Wiring
Using the FDI-INC-2000
Note: Colors indicated are for
wires coming out of lighting zone
controller.
Distribution Panel
Ground
Neutral
Hot (120 V
Mounting the Load Interface
The FDI-FTU-16A-120 and the FDI-INC-2000 mount
into a 4 x 4 in. (102 x 102 mm) junction box of a
minimum depth of 3 in. (76 mm). The interfaces can
also be mounted in a 2-gang wallbox with a minimum
depth of 3 in. (76 mm).
Note: The load interface must only be mounted into a
metal junction box that is properly grounded.
Caution! Be sure all the power wires are
completely inside the junction box before
tightening the mounting screws.
Green
White
Black
Red
(120 V
)
Orange
100-277 V
50/60 Hz
R
16 A Max.
Coopersburg, PA 18036 USA
www.lutron.com
®
DMW-LZC1
Lighting Zone Controller
LISTED
Controlador de zona de luz
Energy Management
Contrôleur de zone d'Éclairage
Equipment 5C81
)
Pour installation, référer au
For installation, refer
Para la instalación, consulte
to the Lighting Zone
la Guía del Instalador de
guide Contrôleur de zone
Controller Installer's Guide
Controlador de zona de luz
d'Éclairage de l'installateur
(p/n 031-268).
(p/n 031-268).
(p/n 031-268).
USA, Canada
1-800-523-9466
Mexico
1-888-235-2910
®
LZC LINK
ADDR
1
2
3
4
5
6
7
8
9
10
11 12 13 14 15
P/N 500-9066 Rev. F
R
(continued)
Ground
Neutral
Neutral
Dimmed hot
Hot in
UP
UP
output
Control
FDI-INC-2000
Incandescent/magnetic
low-voltage interface
To additional
Installation Guide for Lighting Zone Controllers
This page applies to:
Small
Panel
LZC1
Fixture ground
Fixture ground
fixtures
Std.
Panel
29