Lighting zone controller and lighting zone controller panels

Advertisement

Wiring
(continued)
Standard Panels: Conduit Entry
Danger! Locate and lock the supply breaker in
the OFF position, or remove the supply fuse
before continuing.
Standard Panel with Main Lugs
PELV
(Class 2:
USA)
wiring only
PELV
(Class 2:
USA)
wiring only
Preferred feed
wiring entry
Notes: Standard Panel with Main Lugs
• Feed wiring (mains voltage wiring), main input lug
rating:
- (1) #4 AWG thru 250 MCM (25-120 mm
Cu/Al only
- Torque to 250 in-lb (30 N•m)
• Standard panels with main lugs accept the following
- DMWP12-1204ML-20: 200 A, 120/208 V
- DMWP18-1204ML-20: 200 A, 120/208 V
- DMWP12-2774ML-20: 250 A, 277/480 V
- 50/60 Hz, phase-to-neutral
• Maximum rated load per circuit is 16 A
12
Installation Guide for Lighting Zone Controllers
PELV
(Class 2:
USA)
wiring only
Switch legs and
dimmed legs to
loads
PELV
Ground/earth
(Class 2:
connection
USA)
wiring only
Notes: Standard Feed-Through Panel
• Feed wiring (mains voltage wiring):
#10-#14 AWG (6.0-2.5 mm
2
) per lug,
• Standard feed-through panels accept the following:
- DMWP12-FT: 12 separate 15 or 20 A feeds
(16 A maximum per circuit)
- DMWP18-FT: 18 separate 15 or 20 A feeds
(16 A maximum per circuit)
- DMWP24-FT: 24 separate 15 or 20 A feeds
(16 A maximum per circuit)
- 50/60 Hz, single phase
• Maximum rated load per circuit is 16 A
Standard Feed-Through Panel
)
2
This page applies to:
Std.
Panel
Feed wiring
from distribution
panel (typical
for all circuits)
Feed and load
wiring entry
Feed wiring
ground/earth
connection