Appendix: Emergency Mode
Wiring Method Two (continued)
Switch S1: Entire system will go into emergency mode when switch S1 is open.
GRAFIK
7000 System
TM
NTOMX-45J
4 3 2 1
(used only if UI link
is connected
through RS485)
Switch S1
(normally
closed)
Switch S2: Router Panel 1 or GRAFIK 7000P processor panel 1 will go into Emergency mode when switch S2 is
open. Router Panel 2 or GRAFIK 7000P processor panel 2 is unaffected by switch S2.
GRAFIK
7000 System
TM
IP Link*
PP Link
IP Link*
Switch S2
(normally
+V
closed)
Common
*To enable interprocessor communication, either the IP
link's MUX and MUX connections must be wired
together, or the Ethernet communication option must
be used. See the GRAFIK Systems Centralized
Lighting Control System Installation and Maintenance
Guide for details.
Digital microWATT
To COM on UI link
To MUX on UI link
To MUX on UI link
To +33V IP on IP link* of first processor
To SENSE on PP link of all processors
To COM on IP link*
(tie together all processors)
PP Link
Switch S2
(normally
closed)
To SENSE on PP link of other processors
To COM on IP link* of other processors
R
(continued)
System
TM
NTOMX-62J
4 3 2 1
Digital microWATT
Common
{
Emergency
To
NTOMX-62J
MUX
or previous
MUX
router panel
Installation Guide for Lighting Zone Controllers
This page applies to:
Small
Panel
LZC1
Switch S1
(normally
closed)
To EMERG on GUI link
To COM on GUI link
To +V of first router panel
To MUX on GUI link
To MUX on GUI link
System
TM
GUI
GUI
Link IN
Link OUT
Switch S2
(normally
closed)
Std.
Panel
}
To next
router
panel
33