Wiring the LZC Link
Danger! Locate and lock the supply breaker in
the OFF position, or remove the supply fuse
before continuing.
Caution! Make sure power to all LZCs is OFF
during link wiring.
LZC link from Digital
microWATT router panel,
GRAFIK 7000P
processor, or another
lighting zone controller
Notes
• LZC wiring is daisy-chained (from one panel or LZC1
to the next). Pigtails/T-taps must be a maximum
length of 6 inches (150 mm).
• The maximum number of LZCs per link is 63. Panels
contain more than one LZC; take into account the
number of LZCs per panel when calculating LZCs on
each link.
20
Installation Guide for Lighting Zone Controllers
Lutron GRX-CBL-46L
series cable
or equivalent
#22 AWG (0.64 mm
2
)
MUX (white)
#22 AWG (0.64 mm
2
)
MUX (purple)
#12 AWG (2.5 mm
2
)
Link common (black)
#12 AWG (2.5 mm
2
)
Emergency (red)
#24 AWG (0.5 mm
2
)
Shield (bare)
Pigtail wiring configuration:
Pigtails must be less than 6
inches (150 mm) from wire
connector to terminal block
LZC link
terminals
• Wire colors shown assume GRX-CBL-46L is used.
The orange wire is unused.
• The LZC link is considered PELV (Class 2: USA). Do
not run in the same conduit as line voltage.
This page applies to:
Small
Std.
Panel
Panel
LZC1
~
R
100-277 V
100–277 V
50/60 Hz
50/60 Hz
R
Coopersburg, PA 18036 USA
16 A Max.
16 A Max.
Coopersburg, PA 18036 USA
DMW-LZC1
www.lutron.com
Lighting Zone Controller
Integrated Lighting Automation System
Controlador de zona de luz
DMW-LZC1
LISTED
DMW-LZC1 (Lighting Zone Controller)
Contrôleur de zone d'Éclairage
Lighting Zone Controller
Energy Management
LISTED
LUTRON
Controlador de zona de luz
Coopersburg, P A 18036
®
Energy Management
Equipment 5C81
®
Contrôleur de zone d'Éclairage
Equipment 5C81
For installation, refer to
Para la instalación,
Pour installation, référer au
POWER INDICA
TOR
STATUS INDICA TOR
ADDRESS
the Digital microWATT
consulte la Guía del
Pour installation, référer au
guide pour quincaillerie
For installation, refer
On: Caution unit has
Para la instalación, consulte
Continuous double blink: Unit is
SWITCH
Hardware Installer's
to the Lighting Zone
la Guía del Instalador de
Instalador de Digital
guide Contrôleur de zone
Digital microWATT
power
operating properly
Please see installer's
Guide (p/n 031-268).
Controller Installer's Guide
Controlador de zona de luz
microWATT Hardware
d'Éclairage de l'installateur
(p/n 031-268) de
Off: Unit is not powered or
Third blink: Unit is communicating
guide for addressing
(p/n 031-268).
(p/n 031-268).
(p/n 031-268).
l'installateur.
(p/n 031-268).
is not functioning
with command center
information.
properly
On or off continuously: Unit is
(p/n 031-198)
not operating properly
USA, Canada
1-800-523-9466
TEL
FAX
1-800-523-9466
Questions? Call Lutron T echnical Support Center
(24 hrs/7 days)
USA, Canada
Mexico
1-800-523-9466
1-888-235-2910
1-610-282-0298
www.lutron.com
or visit our web site at www
.lutron.com
Mexico
1-888-235-2910
1-610-282-1243
www.lutron.com
Daylight
W all
Occupant
Digital Link
Sensor
Control
Sensor
Digital Link
®
Enlace Digital
LZC LINK
ADDR
LUTRON
LUTRON
Lien Digital
1
2
3
4
5
6
7
8
9
10
11 12 13 14 15
1
2
3
4
5
6
7
8
9
10
11 12 13 14 15
P/N 500-9066 Rev. F
P/N 500-9066 Rev. F
P/N 500-9066 Rev . D
CLASS 2 LOW VOL
T AGE WIRING
To additional LZCs
or LZC panels
(63 LZCs maximum per link)
R
®
R

Advertisement

loading