Lighting zone controller and lighting zone controller panels

Advertisement

Wiring
(continued)
Panel Wiring: General Notes
See the following two pages for details on wiring loads
to the small and standard panels.
• The only dimmed loads that can be connected directly
to an LZC panel are fluorescent fixtures containing
Lutron Hi-lume
or Eco-10
®
load types (120 V
only) require the use of a load
interface available from Lutron. For wiring information
refer to the instructions supplied with the load interface.
• All line voltage connections to the loads must be made
using the load wiring terminal blocks located on the
right hand side of the panel. There are up to 24 sets of
terminal blocks, each containing an orange, red, black,
green/yellow, and two white terminal blocks. Each set
of terminal blocks is connected to a particular LZC. The
number of each LZC is listed on the terminal block
label.
ballasts. Other dimmable
TM
R
Wiring dimmed loads:
• DIMMED HOT connects to the orange terminal block.
If there are no dimmed loads, DO NOT connect any wires
to the orange terminal block.
• SWITCHED HOT connects to the red terminal block
• GROUND connects to the green/yellow terminal block
• NEUTRAL connects to the white terminal block
Wiring switched loads (see page 10 for compatible loads):
• SWITCHED HOT connects to the red terminal block.
• GROUND connects to the green/yellow terminal block.
• NEUTRAL connects to the white terminal block
Installation Guide for Lighting Zone Controllers
This page applies to:
Small
Std.
Panel
Panel
13