Lutron Electronics DMW-LZC1 Installation And Maintenance Manual page 14

Lighting zone controller and lighting zone controller panels

Advertisement

Wiring
(continued)
Small Panels: Wiring
Connect the input feed wires and the output load wires
to the lighting zone controller as indicated in the wiring
diagrams below. Colors indicated refer to the lighting
zone controller panel terminal block and ballast wire
colors.
Small Feed-Through Panel
Input feed and
output line voltage terminals
Orange (DH1)
Red (SH1)
Black (H1)
Green/Yellow (G1)
White (N1)
White (N1)
Orange (DH2)
Red (SH2)
Black (H2)
Green/Yellow (G2)
White (N2)
White (N2)
Small Panel with Main Lugs
Output line voltage terminals
Orange (DH1)
Red (SH1)
Black (H1)
Green/Yellow (G1)
White (N1)
White (N1)
Orange (DH2)
Red (SH2)
Black (H2)
Green/Yellow (G2)
White (N2)
White (N2)
14
Installation Guide for Lighting Zone Controllers
Bypass jumper (do not remove at this
Orange
Black
Green
White
(do not use)
Black
Green
White
Bypass jumper (do not remove at this
Orange
Black
(do not use)
Green
(do not use)
White `
(do not use)
Black
(do not use)
Green
(do not use)
White
Danger! Locate and lock the supply breaker in
the OFF position, or remove the supply fuse
before continuing.
time)
Hot 1
Neutral 1
Hot 2
Neutral 2
Lutron 3-wire
dimming ballast
Fixture ground
Note: For switchable loads (non-dimming),
make sure address switch 8 on the LZC is in
the ON position.
Switched load
Fixture ground
Note: Feed wiring is attached to terminal block
at upper right corner of panel.
time)
Lutron 3-wire
dimming ballast
Fixture ground
Note: For switchable loads (non-dimming),
make sure address switch 8 on the LZC is in
the ON position.
Switched load
Fixture ground
This page applies to:
Small
Panel
From
distribution
panel
Note:
Maximum wire
length from
DMW-LZC1 to
last dimming
ballast is 750
feet (240 m).
Note:
Maximum wire
length from
DMW-LZC1 to
last dimming
ballast is 750
feet (240 m).