CT Wiring Diagram Notes

Note 1
FUSE 2 and contactor may not be required if input power line is neutral. Also see Note 9.
Note 2
Allow 30 seconds after turning power off before reapplying power
Note 5
All AC Line wires should be twisted pair
Note 6
The ground of the drive and motor best minimizes ground currents and noise when connected
in a "star point" configuration
Note 9
See BUS Electrical Specifications on page 12 for recommended line input fusing.
Note 10
Cables should be properly bonded to the backpanel and implemented as close to the drive
side of the cable as possible for effective grounding. If bonding is installed, the shield on the
cable end need not be connected to the "star point" configuration. Only connect the shield on
one end of the cable; preferably on the drive side. See Installation Practices on page 21 for
full details.
Note 11
Units must be installed in an enclosure that meet the environmental IP rating of the end
product ( ventilation or cooling may be necessary to prevent enclosure ambient from
exceeding 45°C).
Note 12
Reserved
Note 13
See SERVOSTAR CT Hardware Specifications on page 16 and BUS Module Hardware
Specifications on page 18 for wire gauge and ferrule sizes.
Note 14
Reserved
Note 16
See SERVOSTAR CT Hardware Specifications on page 16 and BUS Module Hardware
Specifications on page 18 for spade and ring terminal sizes.
Note 17
This system is suitable for use on a circuit capable of delivering not more than 5000 RMS
symmetrical amperes, 240V maximum.
28
®
SERVOSTAR
SBD-Series ST/CT Product Family
Hardware Installation