Configuring The Lonworks Communication; Network - Daikin MicroTech III Troubleshooting Manual

Software download
Hide thumbs Also See for MicroTech III:
Table of Contents

Advertisement

Configuring the LonWorks
Communication Network
The following section describes how to create a LonWorks
communication network drawing and import the WSHP Device
Template into the network using CT.
1. Open the Echelon IzoT Commissioning Tool. The Design
Manager screen appears
Figure 50: IzoT Commissioning Tool Design Manager
2. Either create a new network or select an existing

network.

a. To select an existing network:
i. Select the network from the Drawing directory
drop-down menu.
ii. Click on Open Network.
iii. Proceed to the Commissioning the LonWorks
Communication Module section.
b. To create a new network:
i. Enter a name in the Network name field and
then click Create Network.
3. Select the Network Interface Name
determined from step 5 of the Installation and Setup
section
(Figure
48).
www.DaikinApplied.com
(Figure
50).
(Figure 51)
as
Download and Configuration - LonWorks
Figure 51: LonWorks Interface Name
4. Click Next.
5. Verify the Management Mode is OnNet and click Finish
(Figure
52).
Figure 52: Management Mode
6. A screen similar to
7. Drag the Device icon (shown on the left-hand side of the
image in
Figure
Figure 53: LNS Network Interface Screen
25
OM 1085-6 • MICROTECH III CONTROLLER
Figure 53
appears.
53) to the center of the screen.