Omron SYSMAC C200HW-ZW3AT2-E-V2 Operation Manual page 49

Table of Contents

Advertisement

Connecting to a Node
CQM1H PCs
Communications Port 2
Byte
b7 b6 b5 b4 b3 b2 b1 b0
[+10]
b7 b6 b5
0
0
0
1
0
1
1
0
1
0
b7 b6 b5 b4 b3 b2 b1 b0
[+11]
b7 b6 b5 b4 b3 b2 b1 b0
[+12]
Specify an Xoff (send stop) code.
The initial value is 13 Hex and the bit string is as follows:
b7 b6 b5 b4 b3 b2 b1 b0
[+13]
Specify an Xon (send stop release) code.
The initial value is 11 Hex and the bit string is as follows:
b7 b6 b5 b4 b3 b2 b1 b0
[+14]
Specify the transmission delay.
The initial value is 00 Hex (0 ms) and the bit string is as follows:
Set all bits of bytes [+15] to [+19] to 0.
Connecting to Peripheral Port
Use one of the following methods when connecting to the peripheral port on the
CPU Unit.
a) Set DIP switch pins 5 and 7 to ON, and set the baud rate for the Controller
Link Support Software to 9,600 bps.
0
Data length
0: 7 bits
1: 8 bits
Parity
0: Even
1: Odd
Parity check
0: Yes
1: No
Stop bits
0: 2 bits
1: 1 bit
Baud rate
0
9,600 bps
0
2,400 bps
1
4,800 bps
0
9,600 bps
1
19,200 bps
0
0
0
0
0
Retries
0: No
1: Yes
Communications mode
0: Full duplex
1: Half duplex
Xon/Xoff control:
0: No
1: Yes
13 Hex = 0001 0011
11 Hex = 0001 0001
00 Hex = 0000 0000
Section
3-3
35