Error Messages
Error message
No CLK board/driver
No DataLink table – can't run
No drive
No part of DataLink
No polling node – can't run
No print data
No space
No such data
No such PC ID
No unit
No write area – can't write
Not in DataLink – can't monitor
Not in DataLink – can't write
Not in network
Not initialized
Out of range
Parameter err
Printer err
Receive time-out
Relay err Netwk(???) Node (???) An error has occurred in the PC for
Response time out
Routing table error
146
Cause
A Controller Link Support Board is not
installed in the computer or the driver is
not set correctly.
Cannot be executed because the data
link table has not been registered.
No floppy disk, memory card, or hard
disk exists in the specified drive.
The specified node is not participating in
the data links.
Cannot be executed because the
specified node is not a polling node.
The specified data cannot be processed. Specify the correct data.
The file cannot be saved because of
insufficient free space on the data disk,
memory card, or hard disk.
The specified search data does not exist. Enter the correct search data.
The specified PC ID does not exist.
The specified unit does not exist.
The write area (transmission area) for
the local node does not exist.
The data link table has not been set or
the local node is not participating in the
data links.
The data link table has not been set or
the local node is not participating in the
data links.
The specified node is not participating in
the network.
The floppy disk or memory card has not
been formatted. Files cannot be saved
on unformatted floppy disks or memory
cards.
The specified word address is above the
maximum limit.
The specified parameter is incorrect.
The Controller Link Support Software is
not correctly connected to the printer.
The printer is not in ready status.
The printer or printer cable is faulty.
A receive timeout error has occurred.
relaying between networks.
A timeout error has occurred because a
response to the communications
command was not received from the
destination unit.
The routing tables are set incorrectly.
Appendix A
Action to be taken
Install a Controller Link Support Board or
set the driver correctly, then start again.
Register the data link table.
Insert a floppy disk or memory card into
the specified drive or check the specified
drive name.
Check all nodes that are participating in
the data links.
Check the node on the network.
Delete unnecessary files from the data
disk, memory card, or hard disk or use a
new data disk or memory card.
Check the specified PC ID and specify
the correct PC ID.
Check the specified PC ID and the PC ID
registered in the computer.
Check the I/O configuration and the
network configuration.
Check the data link tables set for the
local node.
Check the data link table set for the local
node.
Check the data link table set for the local
node.
Check all nodes on the network.
Format the floppy disk or memory card
before saving the files.
Specify a word address within the
allowable range.
Specify the correct parameter.
Press the Escape Key first, then check
whether the cable between the Controller
Link Support Software and the printer is
correctly connected.
Check whether the printer is in ready
status.
Check the printer and printer cable.
Increase the maximum node response
time and then execute again.
Check the PC for relaying between
networks.
Check the destination unit.
Check the routing tables.