Using Modems
Set a unit number between 0 and 31. Other items must be set exactly as shown above.
Modem Settings
This section describes example modem settings. Perform an equivalent setup by referring to the user's manual for
your modem.
Note 1. For the modem at the PC, always store the settings in the nonvolatile memory in the modem.
2. In this section, the procedure for storing the settings in the nonvolatile memory in the modem is de-
scribed. This procedure does not necessarily have to be performed for the modem at the computer. If,
however, the settings are not stored in the nonvolatile memory, the modem will need to be set up using
AT commands from the communications software each time a communications procedure is started.
Setting Items
The items shown in the following table must be always set.
Other setting items differ according to the telephone line type, modem type, and so on.
Set each item according to your system as described for specific modems.
DM 6645
Mode setting
0001 Hex
1:1 Link area
CTS control setting
Standard
communications
conditions
DM 6646
Baud rate
0003 Hex
Data length
Stop bits
Parity
Unit No.
DM 6647
Transmission delay
0000 Hex
Item
Baud rate
Data bits
Parity
Stop bit
Data error correction and data
compression
Flow control
Automatic reception
ER signal
Fixed terminal line speed mode
Abort timer
According to DM 6646
settings
9,600
7
1
Even
0
0
Setting details
2,400, 4,800, 9,600, or 19,200 bps
7 bits
Even
1 bit
Data error correction enabled
Data compression disabled
MNP class 4, or V.42, etc.
Disabled (CS/RS control disabled and Xon/Xoff
control disabled)
Enabled (at PC)
Always ON
Disabled
Set to 10 minutes (example value)
Appendix B
Bits/s
Bits
Bits
10 ms