Air Purge Valve - Johnson Controls SABROE ComPAC Operating Manual

Chiller unit with screw compressor
Hide thumbs Also See for SABROE ComPAC:
Table of Contents

Advertisement

Design and function
3.2.7

Air purge valve

If there is air in the refrigeration plant, it tends to accumulate in the receiver or the condenser.
On ComPAC (water-cooled condenser), the air purge valve is fitted at the top of the HP float valve
cover at the bottom of the condenser, Fig. 14, pos. 3.
Note: The valve at the bottom of the cover, Fig. 14, pos. 4, is used for liquid draining (R717).
During air purging the air purge valve should be connected to an open vessel containing water via
a refrigerant hose.
The air will leave the water as bubbles whereas the R717 gas will be absorbed by the water.
Note: R717 containing water must be disposed of in a correct and proper way, see chapter 2.3.9
Purging a refrigeration plant.
Operating manual - ComPAC
32/56
011769 en 2020.03