Engineering Data - Omron S82K Manual

Switching power supply
Hide thumbs Also See for S82K:

Advertisement

S82K
J REFERENCE VALUE
Item
Value
Reliability (MTBF)
135,000 hrs min.
Life expectancy
8 yrs. min.

Engineering Data

J DERATING CURVE
3-/7.5-/15-/30-/50-/90-W/
100-W Models
Installation B
S82K-03005
Installation A
Ambient temperature ( C)
Note: When using the 7.5-W single-output
models within the input voltage range
between 90 and 110 VDC, the load
rate will become 90% or less.
When using the 90-W model at an
ambient temperature exceeding
25 C, the load rate will become 90%
or less.
Mounting Position
The derating curve can be ensured for these two kinds of installations.
(A) Standard (Vertical) Installation
Top
Definition
MTBF stands for Mean Time Between Failures, which is calculated according to the
probability of accidental device failures, and indicates reliability of devices.
Therefore, it does not necessarily represent a life of the product.
The life expectancy indicates average operating hours under the ambient
temperature of 40 C and a load rate of 50%. Normally this is determined by the life
expectancy of the built-in aluminum electrolytic capacitor.
240-W Model
Single-Unit Operation
Installation A
Installation A
S82K-P24024:
100-VAC input
(see note)
Ambient temperature ( C)
Note: 100-V input: 85 to 132 VAC
(B) Horizontal Installation
Top
Parallel-Unit Operation
Note: Not permitted for 240-W models.
S82K
Installation A
200-VAC input
S82K-P24024:
100-VAC input
Ambient temperature ( C)
7