6.6

Output Wiring

The output wiring of the CPU modules, I/O modules, and terminal modules is explained below.

Transistor output

For output specifications of the CPU modules, refer to Page 20 Output Specifications. For
output specifications of the I/O modules, refer to Page 116 Output specifications.
For output specifications of the terminal modules, refer to
Sink and source output
Sink output and source output products are available for transistor outputs of the CPU module, I/O modules, and
terminal modules.
■Differences in circuit
• Sink output [-common]
Output to make load current flow into the output (Y) terminal is
called sink output.
Load
Y
*1
COM
Fuse
DC power
supply
*1 The number "0" or "1" is applied in
Handling of transistor output
■Output terminal
8 transistor output points are covered by one common terminal.
Sink output
The COM
(number) terminals that are connected each other
inside the PLC are prepared. For external wiring, connect the
COM
(number) terminals outside the PLC to reduce the load per
one COM
terminal.
Sink output type
Load
Y000
Y001
Fuse
COM1
5 to 30 V
COM1
DC
■External power supply
For driving the load, use a smoothing power supply of 5 to 30 V DC that can output a current two or more times the
current rating of the fuse connected to the load circuit.
■Insulation of circuit
The internal circuit of the PLC and the output transistor are insulated with a
photocoupler. The common blocks are separated from one another.
■Display of operation
With the DISP switch set to OUT, the LED turns on and the output transistor turns on when photocouplers are actuated.
6 WIRING
• Source output [+common]
Y
.
PLC
Page 127 Output specifications.
Output to make load current flow out of the output (Y) terminal is
called source output.
Load
Fuse
*1
+V
DC power
supply
Source output
The +V
(number) terminals that are connected each other inside the
PLC are prepared. For external wiring, connect the +V
terminals outside the PLC to reduce the load per one +V
Source output type
Load
Y000
Y001
5 to 30 V
DC
+V0
Fuse
+V0
(number)
terminal.
PLC