Input specifications
There is the simultaneous ON ratio of available PLC inputs or outputs with respect to the ambient temperature. For details,
refer to
Page 20 Input/Output Derating Curve.
Item
No. of input points
FX5-C32EX
FX5-C32ET
FX5-8EX/ES
FX5-16EX/ES
Connection type
FX5-C32EX
FX5-C32ET
FX5-8EX/ES
FX5-16EX/ES
Input type
FX5-C32EX/D,
FX5-C32ET/D
FX5-C32EX/DS,
FX5-C32ET/DSS,
FX5-8EX/ES,
FX5-16EX/ES
Input signal voltage
Input signal current
Input impedance
Input sensitivity current
ON
OFF
Input response time
Input signal format
Input circuit insulation
Indication of input operation
Input circuit
FX5-C32EX/D,
configuration
FX5-C32ET/D
FX5-C32EX/DS,
FX5-C32ET/DSS
FX5-8EX/ES,
FX5-16EX/ES
Specifications
32 points
16 points
8 points
16 points
Connector
Terminal block (M3 screws)
Sink
Sink/source
24 V DC +20%, -15%
4 mA/24 V DC
5.6 kΩ
3.0 mA or more
1.5 mA or less
ON: 50 µs or less
OFF: 150 µs or less
No-voltage contact input
Sink: NPN open collector transistor
Source: PNP open collector transistor
Photo-coupler insulation
LED is lit when input is on
24 V DC
Photocoupler
COM
X
5.6 kΩ
Sink input wiring
24 V DC
Photocoupler
COM
X
5.6 kΩ
Sink input wiring
24 V DC
Photocoupler
S/S
X
5.6 kΩ
Source input wiring
24 V DC
Photocoupler
COM
X
5.6 kΩ
Source input wiring
24 V DC
Photocoupler
S/S
X
5.6 kΩ
APPEND IX