Mitsubishi Electric MELSEC iQ-F Series User Manual page 176

Hide thumbs Also See for MELSEC iQ-F Series:
Table of Contents

Advertisement

Input specifications
There is the simultaneous ON ratio of available PLC inputs or outputs with respect to the ambient temperature. For details,
refer to
Page 20 Input/Output Derating Curve.
Item
No. of input points
FX5-C32EX
FX5-C32ET
FX5-8EX/ES
FX5-16EX/ES
Connection type
FX5-C32EX
FX5-C32ET
FX5-8EX/ES
FX5-16EX/ES
Input type
FX5-C32EX/D,
FX5-C32ET/D
FX5-C32EX/DS,
FX5-C32ET/DSS,
FX5-8EX/ES,
FX5-16EX/ES
Input signal voltage
Input signal current
Input impedance
Input sensitivity current
ON
OFF
Input response time
Input signal format
Input circuit insulation
Indication of input operation
Input circuit
FX5-C32EX/D,
configuration
FX5-C32ET/D
FX5-C32EX/DS,
FX5-C32ET/DSS
FX5-8EX/ES,
FX5-16EX/ES
Specifications
32 points
16 points
8 points
16 points
Connector
Terminal block (M3 screws)
Sink
Sink/source
24 V DC +20%, -15%
4 mA/24 V DC
5.6 kΩ
3.0 mA or more
1.5 mA or less
ON: 50 µs or less
OFF: 150 µs or less
No-voltage contact input
Sink: NPN open collector transistor
Source: PNP open collector transistor
Photo-coupler insulation
LED is lit when input is on
24 V DC
Photocoupler
COM
X
5.6 kΩ
Sink input wiring
24 V DC
Photocoupler
COM
X
5.6 kΩ
Sink input wiring
24 V DC
Photocoupler
S/S
X
5.6 kΩ
Source input wiring
24 V DC
Photocoupler
COM
X
5.6 kΩ
Source input wiring
24 V DC
Photocoupler
S/S
X
5.6 kΩ