Mitsubishi Electric MELSEC iQ-F Series User Manual page 197

Hide thumbs Also See for MELSEC iQ-F Series:
Table of Contents

Advertisement

Output specifications
■Relay output (FX-16EYR-TB, FX-16EYR-ES-TB/UL)
Item
Output type
External voltage
Max. load
Resistance load
Inductive load
Min. load
Open circuit leakage current
Response time
ON voltage of output element
Insulation of circuit
Indication of output operation
Power consumption
Input/output configuration circuit
FX-16EYR-TB
FX-16EYR-ES-TB/UL
Unsupported applications
Specifications
Relay
250 V AC or less, 30 V DC or less
2 A/point
The total load current per common terminals (four points) should be 8 A or less.
80 VA
5 V DC, 2 mA (reference values)
Approx. 10 ms
1.5 V
Mechanical insulation
LED is lit when the power is supplied to relay coils.
1.92 W (80 mA 24 V DC)
24 V DC 5 mA
24+
CN1
connector
side
LED
24 V DC 5 mA
24-
CN1
connector
side
LED
Positioning, Pulse Y Output ((D)PLSY) instruction, Pulse Width Modulation ((D)PWM) instruction,
ABS Current Value Read (DABS) instruction, Start/stop of high-speed I/O function ((D)HIOEN)
instruction, Input Matrix (MTR) instruction, Digital Switch (DSW) instruction, Seven Segment With
Latch (SEGL) instruction
0 to 7
Fuse
COMn
External wiring
0 to 7
Fuse
COMn
External wiring