Analog Input Wiring; Analog Output Wiring - Mitsubishi Electric MELSEC iQ-F Series Training Manual

Hide thumbs Also See for MELSEC iQ-F Series:
Table of Contents

Advertisement

Analog Wiring
Wiring to the built-in analog I/O terminals of the CPU module is explained below.

Analog input wiring

Shield
*1
Class D
grounding
*1 For analog input wiring, use shielded twisted-pair cables (double-core type). Separate them from other power lines or lines which can be
induced by others.
*2 For unused channels, short-circuit the "V+" and "V-" terminals.

Analog output wiring

*1
Shield
*2
Class D grounding
*1 For analog output wiring, use shielded twisted-pair cables (double-core type). Separate them from other power lines or lines which can
be induced by others.
*2 Ground a shielded cable at one point on the signal receiving side.
Built-in analog terminal
European type
terminal block
5 poles
Analog
Analog
input
output
82.7 k
V+
V-
33 k
*2
V+
V-
17
CH
CH No. goes in  of V+, CH.

Advertisement

Table of Contents
loading

Table of Contents