CVRC-M-1D
Diagnostics Menu
Clearing Diagnostics
At the end of the diagnostic menu, there will be four screens which
allow the user to Clear/Reset the different diagnostic groups.
1. If any active diagnostics are present, the following screen will be
displayed:
Press (Enter) To Clr Active Diagnostics
And Shutdown/Reset System
If the enter key is depressed, the following message is displayed for
two seconds.
Active Diagnostics Have Been Cleared
The display will be reset to the operating mode screen of the chiller
report after this message clears.
2. If any historic diagnostics are present, the following screen will be
displayed:
Clear Historic Diagnostics
If the enter key is depressed, the following message is displayed for
four seconds.
Historic Diagnostics Have Been Cleared
Diagnostic Report Is Being Reset
The display will be reset to the top of the Diagnostic Menu after this
message clears.
3. If any purge diagnostics are present, the following screen will be
displayed:
Clear Purge Diagnostics
If the enter key is depressed, the following message is displayed for
four seconds.
Purge Diagnostics Have Been Cleared
Clear Purge Diagnostics
4. If any IPC refrigerant monitor diagnostics are present, the following
screen will be displayed:
Silence Rfgt Mon Audible Alarm
Note: Pressing (+) will silence the audible alarm. The IPC refrigerant
monitor will cause all the refrigerant monitor alarms (diagnostics) to
become non-latching for approximately 7.5 seconds. This allows any
latching alarms to clear if the trip condition has been removed. This
clearing function differs from the balance of FastPak in that the
System Is Resetting
Press (Enter) To
Press (Enter) To
Press (+) To