CVRC-M-1D
Machine Configuration
External Analog Input Type Selection. 4-20 ma/2-10 vdc
External Analog Inputs:
Press <+> <-> To Change Setting
Possible values for status are: 2-10 vdc, Factory Default is 4-20 ma.
Note that the Tracer Option will automatically be installed if
communication with a Tracer module occurs.

Tracer Option

Tracer Option:
Press <+> <-> To Change Setting
Possible values for status are: Enable, Factory Default is Disable.

TCI Option

TCI Option:
Press <+> <-> To Change Setting
Possible values of status are: Enable, Factory Default is Disable.
TCI option will automatically be installed if communication with TCI
module occurs.

Printer Option

Printer Option:
Press <+> <-> To Change Setting
Possible values for status are: Installed, Not Installed; Factory Default is
Not Installed.
Duplex Control Module (DCM) Option
DCM Option:
Press <+> <-> To Change Setting
Possible values for status are: Installed, Not Installed; Factory Default is
Not Installed.
Note that the DCM option will automatically be installed if communication
with a DCM module occurs.

IGV Output Type

The pulse option is mutually exclusive with HGBP. If this item is set to
"Pulsed", the "Hot Gas Bypass Option" shall be set to "Not Installed".
IGV Output Type:
Press <+> <-> To Change Setting
Possible values for Status are: Stepper Motor, Pulsed; Factory default
is Stepper Motor.
If Inlet Guide Vane Output is set to Pulsed and Hot Gas Bypass Option is
currently set to installed, the Hot Gas Bypass Option will be set to "Not
Installed" and the following will be displayed for 3 seconds to indicate the
change.
Hot Gas Bypass Option:
Has Been Set to Not Installed
[Type]
[Status]
[Status]
[Status]
[Status]
[Status]