38
Report
The Compressor Report Group sequence is as follows:
Report Heading
Compressor Hours, Starts & Amps
Press <Next> <Previous> To Continue
Differential Oil Pressure, Oil Temperature
The following will be displayed only if the Oil Pressure Protection
Setpoint is set to "Diff. Xducer":
Differential Oil Pressure:
Oil Tank Temperature:
The possible value for [units] is "psid" or "kPa" dependent upon whether
English or SI units are selected.
Differential Oil Pressure, Oil Temperature
The following will be displayed only if the Oil Pressure Protection
Setpoint is set to "Diff. Switch":
Differential Oil Pressure Switch
Oil Tank Temperature:
The possible value for [Status] is "open" or "closed".
AF Compressor Speed Command
The following will be displayed only if the Starter Type is Adaptive
Frequency and Adaptive Speed Control Algorithm is Enabled.
AF Compressor Speed Command:
AF Compressor Speed Command:
Range of Values is 2520 to 3600 RPM in increments of 1 RPM. Factory
Default is 3600 RPM.
AF Boundary Pressure Coefficient/AF Pressure
Coefficient
The following will be displayed only if the Starter Type is Adaptive
Frequency and Adaptive Speed Control Algorithm is Enabled.
AF Boundary Press Coefficient:
AF Pressure Coefficient:
Note: This is a report for Trouble-shooting purposes.
XXX.X [units]
XXX.X F/C
[Status]
XXX.X F/C
XX.X Hz
XXX.X RPM
X.XX
X.XX