Diagnostic Description
External Current Limit Setpoint
HGBP Valve Closure Overdue
Heat Sink Temp Sensor
High Bearing #1 Temp
High Bearing #2 Temp
High Cprsr Discharge Temp.
High Motor Temp Position #1
High Motor Temp Position #2
High Motor Temp Position #3
CVRC-M-1D
Diagnostics Tables
Diag. Active
Diag
Modes
Cause
Type
(Non-Active
Modes)
IFW-
All
a. Not "Enabled": No diagnostics.
AR
b. "Enabled": Out-Of-Range Low or Hi, set diagnostic, default
CLS to next level of priority (e.g. Front Panel SetPoint. This IFW
diagnostic, default CLS to next level of priority (e.g. Front Panel
SetPoint. This IFW diagnostic will automatically reset if the input
returns to the normal range.
IFW
Whenever
a. The HGBP Valve was commanded to close and did not close
going for a
in the three minutes allowed for closure.
HGBP
controlled
mode to an
uncontrolled
mode. e.g.
when
exiting
HGBP, On
Reset, etc.
IFW
All
Open or Short and Solid State Starter Installed.
MMR
All starting
a. The bearing temperature at sensor #1 exceeded 180 + or - 5F
and running
(82.2 C) for 0.5 -2 seconds (Note: BT, WT, and DT may be
modes
"instantaneous trip" but consistent with the analog input filtering
function.), and
b. This function is enabled at the Clear Language Display.
MMR
All starting
a. The bearing temperature at sensor #2 exceeded 180 + or -5 F
and running
(82.2 C) for 0.5 - 2 seconds. (Note: BT, WT, and DT may be
modes
"instantaneous trip" but consistent with the analog input filtering
function.), and
b. This function is enabled at the Clear Language Display.
MAR
All
a. The discharge temp. exceeded the trip value; 200 F + - 5 F.
The Discharge Temp Cutout is adjustable at the Clear Language
Display.
b. Time to trip from trip value exceeded shall be 0.5 to 2.0
second. (Note: BT, WT, and DT may be instantaneous trip" but
consistent with the analog input filtering function.)
c. The diag. shall reset automatically 50 F below the trippoint.
MMR
Any Start
The Motor winding temp. at Sensor #1 exceeded 265 F + or - 15
and Run
F for 0.5 - 2 seconds. (Note: BT, WT, and DT may be
Mode
"instantaneous trip" but consistent with the analog input filtering
function.)
MMR
Any Start
The Motor winding temp. at Sensor #2 exceeded 265 F + or - 15
and Run
F for 0.5 - 2 seconds. (Note: BT, WT, and DT may be
Mode
"instantaneous trip" but consistent with the analog input filtering
function.)
MMR
Any Start
The Motor winding temp. at Sensor #3 exceeded 265 F + or - 15
and Run
F for 0.5 - 2 seconds. (Note: BT, WT, and DT may be
Mode
"instantaneous trip" but consistent with the analog input filtering
function.)
Help Message
Check Signal At Input
Check Clsd
End-Switches, Valves,
Wiring
Check Sensor, Wiring
and Connections
Check Oil System
Check Oil System
See Troubleshooting
Service Bulletin
CVHE-SB-32
See Troubleshooting
Service Bulletin
CVHE-SB-32
See Troubleshooting
Service Bulletin
CVHE-SB-32
See Troubleshooting
Service Bulletin
CVHE-SB-32