CVRC-M-1D
Field Startup
High Discharge Temp Cutout
High Discharge Temp Cutout:
Press <+> <-> to Change Setting
Range of values is 170 to 220 °F (76.6 to 104.4 °C) in increments of 1 or
0.1 °F or °C depending on the Service Setup Screen XXX or XXX.X.
Factory default is 200 °F (93.3 °C).
Soft Load Control Enable
Soft Load Control :
Press <+> <-> to Change Setting
Possible values of [d/e] are: Enable, Factory Default is Disable.
Soft Load Starting Current Limit
Soft Load Starting Current Limit:
Press <+> <- > to Change Setting
Range of values is 40 to 100 % in increments of 1 %. Factory Default is
100%.
Help Note: The unit will start using the set number, i.e.
S O
ramp up to
.
Soft Load Current Limit Rate of Change
Soft Load Current Limit Rate:
Press <+> <-> to Change Setting
Range of values is 0.5 to 5 %/min in increments of 1 or 0.1 %/min
depending on the Service Setup Screen XXX or XXX.,X. Factory default
is 5 %/min.
Help Note: This controls the soft load rate of change.
Soft Load Lvng Wtr Temp Rate of Change
Soft Load Lvg Water Rate:
Press <+> <-> to Change Setting
Range of values is 0.5 to 5 °F/min (0.3 to 2.8 °C/min) in increments of 1
or 0.1 °F/min depending on the Service Setup Screen XXX or XXX.X.
Factory default is 5 °F/min (2.8 °C/min).
Hot Gas Bypass Enable
This screen will be suppressed when the hot gas bypass option is not
installed.
Hot Gas Bypass Control:
Press <+> <-> to Change Setting
Possible values of [d/e] are: Disable; ROM Default, Enable.
XXX.X F/C
[d/e]
XX %
, and
XX %/min
XX F/C/min
[d/e]
61