Machine Configuration

Line Voltage Sensing Option

The following is suppressed if starter type is set to "Stand Alone No Str
Module".
Line Voltage Sensing Option:
Press <+> <-> To Change Setting
Possible values for status are: Installed, Factory default is Not Installed.

Unit Line Voltage

Suppress this screen if the Line Voltage Sensing Option is not installed.
Unit Line Voltage:
Press <+> <-> To Change Setting
Possible values of [Volt] are "180" through "6600" in 5 volt increments.
Factory Default is 460 volts. Factory set per nameplate.

Hot Gas Bypass Option

This option is mutually exclusive with the pulsed IGV output. If this option
is installed, the "Inlet Guide Vane Output" shall be set to "Stepper Motor".
Hot Gas Bypass Option:
Press <+> <-> To Change Setting
Possible values for status are: Installed, Factory default is Not installed.
Condenser Pressure Sensor Option

Condenser Press Sensor Option:

Press <+> <-> To Change Setting
Possible values for status are: Installed, Factory default is Not installed.
Bearing Temperature Sensors Option

Bearing Temp Sensors Option:

Press <+> <-> To Change Setting
Possible values for status are: Installed, Factory default is Not Installed.
Discharge Temperature Sensors Option
Discharge Temp Sensor Option:
Press <+> <-> To Change Setting
Possible values for status are Installed, Factory default is Not Installed.

Ice Building Option

Ice Building Option:
Press <+> <-> To Change Setting
Possible status are: Installed, Not Installed; Factory default.
[Status]
[Volt]
[Status]
[Status]
[Status]
[Status]
[Status]
CVRC-M-1D