Trane CVRC-M-1D Manual page 15

Table of Contents

Advertisement

Menu Item
31
HGBP Vane Position
32
LWT Proportional Gain Setpoint
33
LWT Integral Gain Setpoint
34
LWT Derivative Gain Setpoint
28
IGV MAXIMUM Travel Setpt:
29
Guide Vane Closed Travel Stop
30
AF Adjustable Speed Control Algorithm
31
AF Leaving Water Standard Deviation
32
AF Pressure Coefficient Constant
33
AF Re-Optimization Factor
34
AF Re-Optimization Timer
35
AF Boundary PC Y-Intercept
36
AF Boundary PC Y-Intercept Maximum
37
AF Pressure Error Deadband
38
AF Proportional Speed Gain
39
Minimum Capacity Timer
40
Time Permitted at Min Cap
41
Local Atmospheric Pressure
42
Min Delta Press Calib (2 VDC)
43
Max Delta Press Calib (10 VDC)
44
Inlet Guide Vane Stroke Time
45
Low Diff Oil Pressure Cutout
46
Pre Lube Setpt
47
Post Lube Setpt
48
Check Oil Filter Diagnostic
49
Check Oil Filter Setpt
CVRC-M-1D
FastPak
"Settings Group" Menu Record
Choices
0 to 30%
0 to 100%/ °F
0 to 180%/ °C
0 to 1%/ °F
0 to 1.8%/ °C
0 to 10%/ °F
0 to 18%/ °C
0 to 60,000 Steps
0 to 100%
Disable, Enable
0.5 to 4.0
0 to 2000
0.03 to 1.00
1 to 255
0.01 to 2.00
0.01 to 2.00
0.001 to 1.000
1 to 100
Disable, Enable; Unlimited Time
1 to 480 minutes
10 to 16 psig
68.9 to 110.3 kPa
0 to 400 psid
0 to 2758 kPa
1 to 400 psid
7 to 2758 kPa
15 to 100 seconds
9 to 35 psid
62 to 241 kPa
20 to 60 seconds
30 to 420 seconds
Disable, Enable
Diag Disabled, 9 to 60 psid, 62 to 414
kPa
Default
Design/Actual
10%
10%/ °F
18%/ °C
0.110%/ °F
0.198%/ °C
0.00%/ °F
0.00%/ °C
50,000 Steps
0%
Enable
1.0
800
0.30
24
0.40
2.00
0.030
50
Enable
30 minutes
14.7 psig
101.3 kPa
0 psid
0 kPa
30 psid
207 kPa
45 seconds
12 psid
64 kPa
60 seconds
180 seconds
Disable
15 psid, 103 kPa
15