CVRC-M-1D
Basic Setups
Differential to Stop Setpoint
Differential to Stop Setpoint:
Press <+> <-> to Change Setting
Range of values is 1 to 10 °F (0.5 to 5.5 °C) in increments of 1 or 0.1 °F
or °C depending on the Service Setup Screen XXX or XXX.X Factory
default is 5 °F (2.8 °C).
Evap Pump Off Delay Time
Evap Pump Off Delay:
Press <+> <-> to Change Setting
Range of values is 0 to 30 minutes in increments of 1 minute. Factory
default is 1 minute.
Printer Setups
This screen is shown only when the Printer Option is installed.
(Enter) to Change: (Next) to Continue
If Next is pressed the following printer printer setup screens are skipped.
If Enter is pressed the following screens are displayed to permit
modification of the printer setups.
Print Time Interval:
Press <+> <- > to Change Setting
The choices for Status are: Enable (Factory Default) Disable.
Print on Time Interval:
Press <+> <- > to Change Setting
Range of Values is 1 to 24 Hours in increments of 1 Hour. Factory
Default is 8 Hours.
Print on Diagnostic:
Press <+> <- > to Change Setting
The choices for Status are: Enable (Factory Default) Disable.
XXX.X F/C
XXX Min
Printer Setups
[Status]
XXX Hours
[Status]
53