Refrigerant Report

The Refrigerant Report Group sequence is as follows:
Report Heading
Refrigerant Temp & Pressure Report
Press <Next> <Previous> to Continue
Evaporator and Condenser Refrigerant Pressure
Evap Rfgt Pressure:
Cond Rfgt Pressure:
Saturated Evaporator Temperature/Evaporator
Refrigerant Pressure
Saturated Evap Temp:
Evap Rfgt Pressure:
Saturated Condenser Temperature/Condenser
Refrigerant Pressure
Saturated Cond Temp:
Cond Rfgt Pressure:
Saturated Evap Temperature and Discharge Temperature
The Discharge Temp will be displayed only if the Discharge Sensor
Option is installed.
Sat Evap Rfgt Temp:
Compressor Discharge Temp:
Purge Operating Mode/Purge Status
The following screen shall be suppressed if the selected Purge
Control/Type is "Stand-Alone Purge".
Purge Operating Mode:
Purge Status:
Possible values of [mode] are: Auto, Stop, On and Adaptive.
Possible values of [status] are:
Idle
Running
Pumpout
Service Pumpout
Running - Pumpout Inhibited by low
Temp
Pumpout Maximum Rate Disabled
XXX.X psig
XXX.X psig
XXX.X f/c
XXX.X psig
XXX.X F/C
XXX.X psig
XXX.X F/C
XXX.X F/C
[mode]
[status]
(Condensing Unit is Off)
(Condensing Unit is On)
(Temperature initiated pumpout)
(Pumpout initiated by the service switch)
(Pumpout inhibited by low liquid temp)
(Max. Pumpout Rate alarm disabled)