Lenovo ThinkSystem D2 Manual page 63

Enclosure, modular enclosure, modular enclosure for 6u configuration and thinksystem sd530 compute node messages and codes reference
Hide thumbs Also See for ThinkSystem D2:
Table of Contents

Advertisement

1. Check the event log of system management module and xClarity Controller for any fan or cooling-
related issues or power-related issues.
2. Make sure that the airflow at the front and rear of the chassis is not obstructed and that fillers are in
place and correctly installed.
3. Make sure that the room temperature is within operating specifications.
• FQXSPCA0011N: Numeric sensor [NumericSensorElementName] going high (upper non-
recoverable) has asserted.
This message is for the use case when an implementation has detected an Upper Non-recoverable sensor
going high has asserted.
Severity: Error
Serviceable: Yes
Automatically notify Support: No
Alert Category: Critical - Temperature
SNMP Trap ID: 0
CIM Prefix: PLAT CIM ID: 0498
User Action:
Complete the following steps:
1. Check the event log of system management module and xClarity Controller for any fan or cooling-
related issues or power-related issues.
2. Make sure that the airflow at the front and rear of the chassis is not obstructed and that fillers are in
place and correctly installed.
3. Make sure that the room temperature is within operating specifications.
• FQXSPCA0015J: Sensor [SensorElementName] has transitioned from normal to non-critical state.
This message is for the use case when an implementation has detected a Sensor transitioned to non-
critical from normal.
Severity: Warning
Serviceable: Yes
Automatically notify Support: No
Alert Category: Warning - Temperature
SNMP Trap ID: 12
CIM Prefix: PLAT CIM ID: 0520
User Action:
Complete the following steps:
1. Check the event log of system management module and xClarity Controller for any fan or cooling-
related issues or power-related issues.
2. Make sure that the airflow at the front and rear of the chassis is not obstructed and that fillers are in
place and correctly installed.
3. Make sure that the room temperature is within operating specifications.
• FQXSPCA0017M: Sensor [SensorElementName] has transitioned to critical from a less severe
state.
This message is for the use case when an implementation has detected a Sensor transitioned to critical
from less severe.
Severity: Error
Serviceable: Yes
.
Chapter 3
XClarity Controller events
59