Series Access Power Controllers with Power Supply/Chargers Models Include: eFlow4NA8D eFlow102NA8D - 4A @ 12VDC or 24VDC - 10A @ 12VDC - Eight (8) PTC Outputs - Eight (8) PTC Outputs eFlow6NA8D eFlow104NA8D - 6A @ 12VDC or 24VDC...
Page 2
Destructive Attack - I, Endurance Test - IV, Line Security - I, Stand-by Power - II, III, IV UL Listings for Canadian Installations: ULC-S319-05 - Electronic Access Control Systems. Class I Equipment. CSA C22.2 No.205 - Signal Equipment. Altronix Corp. 140 58th St. Brooklyn, NY California State Fire Marshal European Conformity...
Specifications: ACM8CB Access Power Controller Module: • Eight (8) independently trigger controlled outputs. Output options: a) Eight (8) Fail-Safe filtered power outputs. b) Eight (8) Fail-Secure filtered power outputs. c) Any combination of the above. • Eight (8) Access Control System trigger inputs. Input trigger options: a) Eight (8) normally open (NO) dry trigger inputs.
Installation Instructions: Wiring methods shall be in accordance with the National Electrical Code/NFPA 70/ANSI, The Canadian Electrical Code, Part I, Part II, and with all local codes and authorities having jurisdiction. The product must be located indoors within the protected premises. Power Supply Board LED Diagnostics (pg.
Page 5
14. Installation of tamper switch (Fig. 3a, pg. 8): Mount UL Listed tamper switch (Altronix model TS112 or equivalent) at the top of the enclosure. Slide the tamper switch bracket onto the edge of the enclosure approximately 2” from the right side (Fig. 3a, pg. 8).
Maintenance: Unit should be tested at least once a year for the proper operation as follows: FACP Supervision: To ensure proper connection and operation of the Fire Alarm disconnect hookup please follow the appropriate procedure below: Normally Open Input: Placing a short between terminals marked [T] and [+ INP] will trigger the Fire Alarm Disconnect.
Terminal Identification: Power Supply/Charger Terminal Legend Function/Description Connect 120VAC 60Hz to these terminals: L to hot, N to neutral. L, G, N Do not use terminal marked [G] – DC + Factory connected to ACM8CB board. Trigger EOL Fire Alarm Interface trigger input from a short or FACP. Trigger inputs can be normally Supervised open, normally closed from an FACP output circuit (power-limited input) (Fig.
Power Supply Board Output Voltage Settings: Fig. 1 Fig. 1a Switch Detail Switch On - 12V Switch Off - 24V Access Power Controller Typical Application Diagram (ACM8CB): Fig. 2 Fig. 2a Intact = Dry Input Normally Open (N.O.) Cut = Wet Input Door Releasing FACP FACP...
Page 9
Fig. 3 - eFlowNA8D Series Configuration Fig. 3a Enclosure Edge of Enclosure Tamper Switch (included) To Access Control Panel or UL Listed Reporting Device Tamper Switch OFF - 24V ON - 12V eFlow4NB - power-limited eFlow6NB, eFlow102NB, eFlow104NB - non power-limited Battery and AC Supervision Circuit power-limited...
Page 10
NEC Power-Limited Wiring Requirements for eFlowNA8D Models: Power-limited and non power-limited circuit wiring must remain separated in the cabinet. All power-limited circuit wiring must remain at least 0.25” away from any non power-limited circuit wiring. Furthermore, all power-limited circuit wiring and non power-limited circuit wiring must enter and exit the cabinet through different conduits. One such example of this is shown below.
Hook-Up Diagrams: Fig. 5 Optional hook-up using two (2) isolated power supply inputs (Only applicable on eFlow4NA8D, not evaluated by UL): CUT JUMPERS J1 AND J2 ISOLATED POWER INPUT 12 OR 24 VAC OR VDC (ACM8 POWER) ISOLATED POWER INPUT 12 OR 24 VAC OR VDC (LOCK POWER) Fig.
Page 12
Hook-Up Diagrams: Fig. 8 Normally Open FACP Latching trigger input with reset (This output has not been evaluated by UL): FACP N.O. TRIGGER INPUT N.C. RESET SWITCH JUMPER Fig. 9 Normally Closed: Non-Latching FACP trigger input: FACP N.C. DRY TRIGGER INPUT JUMPER Fig.
Page 13
Notes: eFlowNA8D Series Installation Guide - 13 -...
Page 14
Notes: - 14 - eFlowNA8D Series Installation Guide...
Page 15
1.5” 4.615” (117.2mm) 4.615” (117.2mm) (38.1mm) (38.1mm) Altronix is not responsible for any typographical errors. –––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––– 140 58th Street, Brooklyn, New York 11220 USA | phone: 718-567-8181 | fax: 718-567-9056 website: www.altronix.com | e-mail: info@altronix.com | Lifetime Warranty MEMBER IIeFlowNA8D Series...
Page 16
- UL Listed in the U.S. and Canada. - Local or remote control of up to (2) two Altronix eFlow power output(s) via LAN and/or WAN. - Monitor real time diagnostics: DC output voltage, output current, AC & battery status/service, input trigger state change, output state change and unit temperature.