Mitsubishi Electric MELSEC iQ-R Series User Manual page 280

Programmable controller
Hide thumbs Also See for MELSEC iQ-R Series:
Table of Contents

Advertisement

No.
Name
SD80
Detailed information
1 information
category
SD81 to
Detailed information
SD111
1
APPX
278
Appendix 5 Special Register List
Description
Details
Detailed information
Detailed information 1 information category code is stored.
1 information
category code
b15
(1) Information category code
(2) Not used (fixed to 0)
The following codes are stored into the information category code.
• 0: N/A
• 1: N/A
• 2: Drive number and file name
• 4: Parameter information
• 5: System configuration information
• 6: Frequency information
• 7: Time information
• 24: Failure information
Detailed information
• Detailed information 1 corresponding to the error code (SD0) is stored.
1
• There are six types of information to be stored as shown in (2), (4) to
(7), and (24).
• The type of the detailed information 1 can be acquired from SD80. (The
value of the "Detailed information 1 information category code" which is
to be stored in SD80 corresponds to the number (2), (4) to (7), and (24)
in the following.)
■(2) Drive number and file name
b15
SD81
SD82
SD83
SD90
The following information is stored in SD81.
• b0: Drive No.
• b1: File name
■(4) Parameter information
b15
SD81
Parameter storage
SD82
SD83
SD84
SD85
SD86
SD87
SD97
The following information is stored in SD81.
• b0: Parameter type
• b1: Parameter storage destination
• b2: I/O No.
• b3: Parameter No.
• b4: Network No.
• b5: Station No.
• b6: System information
The parameter type is stored in SD82 (b0 to b7).
• 1: System parameter
• 2: CPU parameter
• 3: Module parameter
• 4: Module extended parameter
• 5: Memory card parameter
The parameter storage destination is stored in SD82 (b8 to b15).
• 2: SD memory card
• 4: Data memory
The I/O No. is stored in SD83. (0xFFFFH if an I/O No. is not assigned.)
The network No. (0 to 120) is stored in SD85. (0 for a master station)
b8b7
(2)
(1)
With or without specification
Drive No.
File name
(first eight characters of Unicode string)
With or without specification
Parameter
destination
type
I/O No.
Parameter No.
Network No.
Station No.
System information
Set by (when to set)
S (error occurrence)
b0
S (error occurrence)
b0
1st character
8th character
b0