5.
Set the FUNCTION/SHUTDOWN switch to the FUNCTION position to select the parameter/event history initialization.
Every time the FUNCTION/SHUTDOWN switch is set to the FUNCTION position, the operation to be performed is changed.
Item
Parameter/event history initialization
For the other function which can be selected in the maintenance mode, refer to the following:
Page 26 Operation mode
6.
Set the BUS RESET/Y STOP/Y OUT switch to the Y OUT position.
The parameter/event history initialization is performed.
The Y STOP LED flashes in orange during the initialization.
7.
Check the LED statuses.
When the parameter/event history initialization is completed normally, the Y STOP LED turns ON in orange.
When the parameter/event history initialization is completed with an error, the ERROR LED flashes in red.
If the parameter/event history initialization is completed with an error, turn the power of this product OFF and perform the
initialization again.
8.
Turn the power of this product OFF.
31 PARAMETER/EVENT HISTORY INITIALIZATION FUNCTION
218
LED status
• READY LED: ON (orange)
• Y STOP LED: ON (orange)
• Other LEDs: OFF