Section 7: Resource Block
January 2022
Table 32.
Sub Index Element Name
1
2
This set of parameters is a structure that stores the five last warnings happened in the actuator
together with the date and the time of the faults; The Warning_1 is the newest and the Warning_5 is
the oldest.
This structure allows to report to the fieldbus interface the warning happened while the fieldbus was
not active.
Table 33.
WARNING_LOG_1
WARNING_LOG_2
WARNING_LOG_3
WARNING_LOG_4
WARNING_LOG_5
The warning codes have the following meanings:
Table 34.
Error Code Element Name
0
1
2
3
4
5
6
7
8
9
48
DATE_TIME
WARNING_CODE
Element Name
DATE
TIME
ERROR CODE
DATE
TIME
ERROR CODE
DATE
TIME
ERROR CODE
DATE
TIME
ERROR CODE
DATE
TIME
ERROR CODE
No error
High torque in opening near max.
High torque in closing near max.
Internal temperature near limits
Main voltage near limits
Maximum contactor cycles
Maintenance request
Motor current
Wrong stroke limits
Bus error
Installation, Operation and Maintenance Manual
Description
Date and time of the warning
Error code of the warning
Description
Date of the warning in position #1
Time of the warning in position #1
Error code of the warning in position #1
Date of the warning in position #2
Time of the warning in position #2
Error code of the warning in position #2
Date of the warning in position #3
Time of the warning in position #3
Error code of the warning in position #3
Date of the warning in position #4
Time of the warning in position #4
Error code of the warning in position #4
Date of the warning in position #5
Time of the warning in position #5
Error code of the warning in position #5
Description
Measured torque 10% lower than the relevant value
configured in torque setup or stroke limit routine.
Measured torque 10% lower than the relevant value
configured in torque setup or stroke limit routine.
Temperature inside the actuator enclosure
higher than 90 °C or lower than –35 °C.
Main voltage out of the correct range (-15% or +10% of the
value stated in the nameplate menu) or wrong frequency.
Maximum number of contactor cycles reached.
Date of the next programmed maintenance reached.
Motor current greater or lower than limits.
The routine that monitors the stroke limits
detect a wrong end of travel condition.
The communication over the fieldbus is no longer active.
MDE 255 Rev. 0
Type
DATE_AND_TIME
UNSIGNED8