Emerson Bettis XTE3000 Installation, Operation And Maintenance Manual page 44

Table of Contents

Advertisement

Section 7: Resource Block
January 2022
20
21
22
23
Table 22.
Value
0x8000 Enable setpoint
0x4000 Open
0x2000 Close
0x1000 Stop
0x0800 ESD command
0x0400 Close interlock
0x0200 Open interlock
0x0080 clear recent data log
0x0040 Set torque reference
24
40
MASK_DIAGNOSTIC
Type: BIT_ENUMERATED
Size: 2 octets
Handling: READ and STATIC WRITE
Default value: 0x0000
This parameter is a mask to create the value of DI channel 32 "Maskable diagnostic status".
Set the bit of DIAGNOSTIC_DATA that you want to affect the result of channel 32.
TORQUE
Type: FLOAT and STATUS
Size: 5 octets
Handling: READ
It is the current torque.
POSTION
Type: FLOAT and STATUS
Size: 5 octets
Handling: READ
It is the current position of the valve.
COMMANDS_READ
Type: BIT_ENUMERATED
Size: 2 octets
Handling: READ
The list of the current command active to the actuator.
Element Name
SETPOINT_READ
Type: FLOAT and STATUS
Size: 5 octets
Handling: READ
It is the current setpoint applied to the valve.
Installation, Operation and Maintenance Manual
Description
The setpoint is active with precedence.
Open command
Close command
Stop command
ESD command
Close interlock command
Open interlock command
Clear recent data log command
Set torque reference command
MDE 255 Rev. 0
Resource Block