The FF2000v4 rev. 3 specific parameters are described here below:
13
Table 18.
Value
0x8000
0x4000 Configuration error
0x2000 Extremely High or Low main supply
0x1000 Lost phase
0x0800 Power supply failure
0x0400 Speed sensor failure
0x0200 Position sensor failure
0x0100 Hardware failure
0x0080 Alarm extended 1
0x0040 Alarm extended 2
0x0020 Alarm extended 3
0x0010 Alarm extended 4
14
Table 19.
Value
0x80000000 Manual operation
0x40000000 NAK motherboard
0x20000000 Local selector in LOCAL
0x10000000 Local selector in OFF
0x08000000 Remote hardwired active
0x04000000 Local stop active
0x02000000 ESD active
0x01000000 Interlock open active
0x00800000 Interlock close active
Resource Block
TOTAL_NOT_OPER_STATUS
Type: BIT_ENUMERATED
Size: 2 octets
Handling: READ
When this parameter is set, the actuator is not available for control neither from Fieldbus
F
interface nor for electrical operations due to one or more of the following
tM
oundation
conditions. Only manual operation by handwheel should be possible.
Element Name
Extremely High or
Low internal temperature
PART_NOT_OPER_STATUS
Type: BIT_ENUMERATED
Size: 4 octets
Handling: READ
The actuator may execute a subset of electric operation due to temporary condition or other
Operator Interfaces may have been activated.
Element Name
Section 7: Resource Block
Description
Temperature inside the actuator enclosure
is greater than 90 °C or lower than –40 °C.
The checksum of the EEPOM memory
that contains the configuration data is wrong.
Main voltage is ±20% exceeding the value stated
in nameplate menu or the frequency is wrong.
Only for 3-phase main supply: The alarm is generated
in case of fault of the phase that does not
supply the actuator transformer.
Power supply failure
Measure of motor speed not valid.
The value of the actuator position is not valid.
The diagnostic program detects some malfunction
in the electronic that control the actuator.
Future use
Future use
Future use
Future use
Description
Manual operation in progress by handwheel.
Failure in communication between the
base card and the bus card.
Local selector on LOCAL position: local commands enabled.
Local selector on OFF position: neither local
nor remote commands enabled.
Local selector on REMOTE position and
Hardwired commands enabled.
Local STOP has been activated while remote
commands were in progress.
ESD operation in progress.
Open Interlock operation in progress.
Close Interlock operation in progress.